EMR-5000
IM02602012E
Parameter Setting via Power-Port-E
Power-Port-E shows within the windows, where parameters are edited also the required access level for the
parameters and settings. The required access authorizations will be verified when the parameter file should be
transferred into the protective device. For the transmission, two options are available.
1. The transfer of
all Parameters. This always requires the Supervisor (administrator) password.
2. The transfer of the
modified Parameters only. It has to be taken into account, the passwords that are required
by this are determined by those parameters, that require the highest passwords (access authorizations).
Example1:
A »
Prot-Lv1«-parameter and a »Prot-Lv2« parameter have been edited and should be transferred. The User
will be asked for the »
Prot-Lv2« password.
Example2:
A »
Prot-Lv1« parameter and a »Prot-Lv2« parameter and a device planning parameter have been changed and
should be transferred. The User will be asked for the »
Supervisor-Lv3« password.
Example3:
A »Prot-Lv1« parameter and a »Prot-Lv2« parameter as well as a »Ctrl-Lv2« parameter have been changed
and should be transferred. The User will be asked for the »
Prot-Lv2« and the »Ctrl-Lv2« password.
Changing of Parameters when using the Power-Port-E - Example
Example: Changing of a protective parameter (to alter the characteristic for the overcurrent protection function I[1] in
parameter set 1).
In case
Power-Port-E is not in operation – start this software.
In case the device data has not been loaded – select
»Data To Be Received From The Device« in menu
»Device«.
Double-click the »Protection Para Icon« in the navigation tree.
Double-click the
»Protection Para Set Icon« in the navigation tree.
Double-click the
»Set 1 Icon« in the navigation tree.
Double-click the
»
protection stage I[1]« in the navigation tree.
In the working window a tabulated overview appears, showing the parameters assigned to this protective
function.
In this table double-click the value/parameter you want to change (here:
»Char«).
Another window (popup) is opened where you can select the required characteristic.
www.eaton.com
378
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...