EMR-4000
IM02602009E
Forcing Analog Outputs*
* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from
Analog Output section.
Principle – General Use
The User MUST ENSURE that the Analog Outputs operate normally after
maintenance is completed.
Do not use this mode if forced Analog Outputs
cause issues in external processes.
For commissioning purposes or for maintenance, Analog Outputs can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Analog Outputs], Analog Outputs can be set by
force:
Permanent; or
Via timeout.
If they are set with a timeout, they will keep their “Forced Value” only as long as this timer runs.
If the timer
expires, the
Analog Output will operate normally.
If they are set as »
Permanent«, they will keep the “Forced Value” continuously.
This menu will show the current value that is assigned to the Analog Output until the User activates the force mode by
calling up the »
Function«. As soon as the force mode is activated, the shown values will be frozen as long as this mode
is active. Now the User can force Analog Output values. As soon as the force mode is deactivated, measured values
will again be shown.
www.eaton.com
809
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...