background image

5

Setup Instructions

EG2-NA Ethernet Gateway

 www.eaton.com

The EG-2-NA has in-built network termination .  If the EG-2-

NA is at the end of the network, ensure the CAN TERM 

jumper is fitted in the Termination ON position .
iCAN devices are ‘daisy-chained’ on the network .  Spurs 

from the Network are not permitted and will result in 

communications problems .  Devices on an iCAN network 

can be wired in any order . Termination is required at both 

ends of the network .

iCAN

Device

iCAN

Device

EG2-NA

T  - Indicates where a termination is required .

iCAN Connectors

Cable type: Cooper LC or Belden 1502R or 1502P

Maximum cable length: 1000 ft . (305 m) * 

Devices per segment: 100 (without bridge or repeater)

* A maximum segment distance of 3200 ft . (1000 m) is 

possible if an additional 12V power supply and bridge/

repeater is used .

Setup Instructions

Ethernet Network

Connect the provided RJ45 (568B) jack to an Ethernet 

Switch or Wireless Router .

Ethernet Input

Configuration

iCAN Device Number

The EG2-NA is supplied with a iCANnet Device number 

with Segment number 255 and a node number in the range 

1-255 . Both Segment and Node number can be changed 

using iCANsoft .

Factory Default IP Settings

IP Address: 192 .168 .0 .100

Mask: 255 .255 .255 .0

Default Gateway: 192 .168 .0 .1

DHCP: Off

otee:

N

The EG2-NA default settings are to use a fixed 

IP address of 192 .168 .0 .100 . Any device used to 

communicate with the EG2-NA will need to be 

located within the 192 .168 .0 .x subnet unless IP 

Address settings are changed .

Power Up

The EG2-NA takes approximately 60 seconds to be ready 

for use once power is applied . Wait for the Green CAN 

LED to flash slowly . The Green Power LED will double flash 

continuously while EG2-NA is on . If Ethernet is connected 

the Link and Data LEDs will indicate successful connection .

Setting the IP Address

The factory set IP Address can be changed using iCANsoft 

software either through a direct PC Node connection 

through the iCANnet or directly into the Ethernet port of the 

EG2-NA .