Mounting

EG2-NA Ethernet Gateway

 www.eaton.com

Mounting

Location and spacing

The EG2-NA should be installed in a dry ventilated location, 

where ambient conditions are maintained within the 

requirements of the unit . 
The unit has ventilation slots on the sides to allow 

convection cooling and in no circumstances should these be 

blocked .
Allow 2” (50mm) above and below the unit if trunking with 

a depth greater than 2” (50mm) is used .

Ambient atmosphere requirements

Temperature: 32°F to 104°F (0°C to +40°C)

Humidity: 20% to 90%, non-condensing

Mounting Holes

The unit is provided with four 0 .25” (6 .35mm) diameter 

fixing holes for wall mounting . The mounting holes can be 

accessed by undoing the four screws on the front cover and 

removing it .

Supply Wiring

Connecting the Supply

This unit requires a 120-240 VAC single phase supply (live 

and neutral) with 0 .45 A capability .
A terminal block is used to connect the incoming feed to 

the internal power supply

Control Wiring

iCAN Network

A removable 5 position terminal block is provided for the 

connection of iCAN network cables .  If the EG2-NA is 

located in the middle of the network, incoming and outgoing 

cables will terminate within the same connector .

Termination OFF

Termination ON

+12V

(Red)

CAN-H

(White)

SHIELD

(Gray)

CAN-L

(Blue)

0V

(Black)

Wire Gauge for Supply Terminals

The live, neutral and earth ground power connections 

are made to the terminal block provided for main power 

connection . Recommended cable size for live, neutral, and 

earth is 26 AWG - 10 AWG .

Live (Gray)

Neutral (Blue)

Earth (Green/Yellow)

Live (Gray)

Neutral (Blue)

Earth (Green/Yellow)