Mounting
Location and spacing
The EG2-NA should be installed in a dry ventilated location,
where ambient conditions are maintained within the
requirements of the unit .
The unit has ventilation slots on the sides to allow
convection cooling and in no circumstances should these be
blocked .
Allow 2” (50mm) above and below the unit if trunking with
a depth greater than 2” (50mm) is used .
Ambient atmosphere requirements
●
●
Temperature: 32°F to 104°F (0°C to +40°C)
●
●
Humidity: 20% to 90%, non-condensing
Mounting Holes
The unit is provided with four 0 .25” (6 .35mm) diameter
fixing holes for wall mounting . The mounting holes can be
accessed by undoing the four screws on the front cover and
removing it .
Supply Wiring
Connecting the Supply
This unit requires a 120-240 VAC single phase supply (live
and neutral) with 0 .45 A capability .
A terminal block is used to connect the incoming feed to
the internal power supply
Control Wiring
iCAN Network
A removable 5 position terminal block is provided for the
connection of iCAN network cables . If the EG2-NA is
located in the middle of the network, incoming and outgoing
cables will terminate within the same connector .
Termination OFF
Termination ON
+12V
(Red)
CAN-H
(White)
SHIELD
(Gray)
CAN-L
(Blue)
0V
(Black)
Wire Gauge for Supply Terminals
The live, neutral and earth ground power connections
are made to the terminal block provided for main power
connection . Recommended cable size for live, neutral, and
earth is 26 AWG - 10 AWG .
Live (Gray)
Neutral (Blue)
Earth (Green/Yellow)
Live (Gray)
Neutral (Blue)
Earth (Green/Yellow)