2. About the EF-CBD130
Beam
Detector
Line-of-Sight Distance
8 to 40m (1 x reflector)
Reflector
1 x Reflector
122mm
100mm
244mm
200mm
4 x Reflector
40m to 100m (4 x reflector)
Figure 6 . mounting of EF-CBD130-R Reflector Reflector
3.6. Cabling Details
Cables should be brought into the detector using the supplied cable gland.
The maximum size of the cable which can be terminated is 1.5mm².
Observe the polarity. Refer to Figure 7.
1. Terminal D1 (+) and D2 (-) for connecting Power supply [24VDC]
2. Terminals S1(+) and S2(-) to be linked to D1 (+) and D2 (-)
3. Terminal HJ1 and HJ2 for connecting Fire signal relay output
[Normally Open]
4. Terminal GZ1 and GZ2 for connecting Fault signal relay output
[Normally Close]
Figure 7 . Wiring terminals