the minimum air flow per battery cabinet is 3.8 m
3
/hour and the
minimum free area of opening for inlet and outlet is 108 cm
2
when
natural ventilation is used.
NOTE: For more information about the battery room ventilation
requirements, including the calculation of the necessary air flow, see:
IEC 62485-2: Safety requirements for secondary batteries and battery
installations.