10.
Roll the cabinet to its final
installation location.
11.
To secure the cabinet in
position, lower the leveling feet
until the cabinet is not resting
on the casters and the cabinet
is level.
NOTE: If you remove the cabinet from its original installation location and
transfer it to a new location on a pallet, lower the leveling feet until the
cabinet is not resting on the casters. In addition, attach the shipping
brackets to the cabinet and the pallet.
3.4
Installing the EBC
.
DANGER
Do not connect battery strings with different battery quantity and
voltage in parallel.
Make sure that the UPS with internal batteries uses 32 battery blocks
per string. External battery strings must also contain 32 battery blocks
per string.