DeviceNet functions
38
09/10 MN05013007Z-EN
easy Object
The easy object can be used to access easy/MFD functions
via the DeviceNet communication bus. The table below
shows the attributes supported by this object. The 2 bytes of
the attributes 1 and 2 give the diagnostics data of the device.
Attribute 3 can be use to access the outputs (S1 to S8) and
attribute 4 to access the inputs (R1 to R16) of the basic unit.
By using a DeviceNet configuration software (e.g.
RS NetWorx), you can map these data directly to the corre-
sponding memory areas of a PLC.
Table 4:
Attribute IDs of the Easy Object instance
Object address
Function
Access
Class ID
Instance ID
Attribute ID
Service code
64
hex
01
hex
Attribute
ID
Access
Name
Description
Size
[byte]
1
Read
easy Status
This attribute can be used to read the
status of easy (RUN or STOP).
1
2
Read
Coupling
Module
Status
This attribute can be used to read the
status of easyLink.
1
3
Read
Inputs – Send
Data
easy transfers the input data to the Devi-
ceNet bus. The easy outputs S1 to S8 must
be used for this function. The structure of
these 3 bytes is described in detail under
Section “Input data: Mode, S1 – S8”,
page 49.
3