Instruction Leaflet 

IL29C119C

Effective August 2011

Installation Instructions for E2F, E2FM Mining Service Circuit Breakers

 

 

EATON CORPORATION

 www.eaton.com

(See accessory schematic diagram on side of cir-

cuit  breaker.)

Note: If terminal shield or interphase barriers are to
be installed on the circuit breaker, install them after

the terminals are connected.

2.6. 

If required, install terminal shield on circuit breaker

cover with mounting screws provided.

2.7.  The supplied interphase barriers should be installed to  

 the line end of the circuit breaker (E²FM1000V only) by

2.8. 

After the circuit breaker is installed, check all

mounting hardware and terminal connecting hard-

ware for correct torque loading. Torque values for

line load terminals are given in Tables 2-1 and 2-2

and on the circuit breaker nameplate.

TABLE 2-1. TERMINAL TYPES

Terminal

Terminal  Screw  AWG

Metric  Wire

Torque  Value

Catalog  Number  Body

Head

Wire

Wire

Type

Lb. In. 

Material

Type

Range  Range

Aluminum  3/16 

#4-4/0   2 5 - 9 5   Cu/AI  1 2 0   ( 1 3 . 6 )

Socket
Hex

Aluminum  5mm

#4-4/0   2 5 - 9 5   Cu/AI  1 2 0   ( 1 3 . 6 )

Socket
Hex

  Aluminum  5/16

#6-300   16-150  Cu/AI  275  (31)

Socket
Hex

 

Aluminum 

 

 

  2.5-50  Cu/AI  See  Table  2-2

Aluminum  Slotted 

  2.5-16 

  See  Table  2-2

 

Steel

Slotted 

 

 

 

  See  Table  2-2

S t a i n l e s s   S l o t t e d  

  2 5 - 9 5   C u

See Table 

y

l

n

O

l

e

e

t

S

Note:  Terminal  wire  connectors  are  UL  listed  for  standard  wire  sizes  as  defined  in
UL 486A and UL 

 of three

 terminal identified as 

TABLE 2-2. TERMINAL TORQUE VALUES FOR 

 HEAD

Metric  Wire

Torque  Value,

AWG  Wire

Torque  Value,

Range

Range

Lb. In.

2.5-6

3.96

35

4.52

40

16-25

5.09

45

35-95

5.65

50

TABLE 2-3. BOLTED CONNECTIONS (KEEPER NUT OR END CAP)

Termination

Nut  Thread

Torque  Value,

Catalog  Number

Size

Lb-In 

 A   

 AM

User  Supplied

1O-32  

35  (4.0)

Slotted

 1O-32   

35  (4.0)

3.0  MANUAL  OPERATION

Manual operation of the circuit breaker is controlled by

the circuit breaker handle and the PUSH-TO-TRIP but-
ton. The circuit breaker handle has three indicated posi-
tions, two of which are shown on the cover with raised

lettering to indicate ON and OFF. On the sliding handle
barrier ON, OFF, and trip are also shown by a color

coded strip for each circuit breaker handle position: red
for ON, white for tripped, and green for OFF. On the slid-

ing handle barrier, ON/OFF is also shown with the inter-
national symbols I/O   (See Fig. 3-1). 

Circuit Breaker Reset

After tripping, the circuit breaker is reset by moving the
circuit breaker handle to the extreme OFF position.

Note: In the event of a thermal trip, the circuit breaker
cannot be reset until the thermal element cools.

PUSH-TO-TRIP  Button

The PUSH-TO-TRIP button checks the tripping function

and is used to periodically exercise the operating mecha-
nism.

Magnetic-Only Mining Service Circuit Breaker 

Adjustment of Trip Setting

The F-frame E   magnetic-only mining service circuit

breaker has a trip setting adjustment mechanism that
permits the circuit breaker to be fine tuned to provide
more precise protection. The mechanism consists of a

cam with eight positions for different trip levels The trip

levels are labeled A through H; actual trip values are
shown on the circuit breaker cover nameplate and in

Table 3-1. To adjust the trip level, depress and rotate

adjustment button clockwise to the desired setting.

CAUTION

A ROTATION STOP PREVENTS THE ADJUSTMENT

BUTTON FROM BEING ROTATED COUNTERCLOCK-

WISE BEYOND POSITION 

A. 

THE CIRCUIT BREAKER

CAN BE DAMAGED IF THE BUTTON IS FORCED
PAST POSITION 

A

 IN THE COUNTERCLOCKWISE

DIRECTION.

 sliding barrier into dovetail grooves between terminals.

2

Screw Head

Type

#4-4/0

#1 4-1/0

#1 4-1/0 2.5-50

Cu/AI

Cu/AI

#1 4-#4

10

2-2

Slotted

Содержание E2F

Страница 1: ...ion 2 2 0 Installation 2 3 0 Manual Operation 4 4 0 Inspection and Field Testing 5 Effective August 2011 Supersedes IL 29C119B Dated 10 01 Instruction Leaflet IL29C119C Installation Instructions for E2 F E2 FM Mining Service Circuit Breakers ...

Страница 2: ...ole devices in several ratings from 3A to 150A continuous current The are avail able in both thermal magnetic and magnetic only ver sions Mining service circuit breakers have been developed to meet the Federal Register ruling on trailing 2 cable protection This instruction leaflet IL gives procedures for the instal lation and field testing of E F and E FM mining service circuit breakers For this p...

Страница 3: ...t mounting panel is predrilled using bolt drilling plan Fig 2 1 For panelboard mounting only load end support mounting holes are required For deadfront cover applications make sure mounting panel cover is cut out to correct escutcheon dimensions Fig 2 2 b If circuit breaker includes factory installed inter nal accessories make sure accessory wiring can be reached when the circuit breaker is mounte...

Страница 4: ...Supplied 1O 32 35 4 0 Slotted 1O 32 35 4 0 3 0 MANUAL OPERATION Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH TO TRIP but ton The circuit breaker handle has three indicated posi tions two of which are shown on the cover with raised lettering to indicate ON and OFF On the sliding handle barrier ON OFF and trip are also shown by a color coded strip ...

Страница 5: ...nical linkages are free and do not bind If mechanical linkages are not free replace circuit breaker Press the PUSH TO TRIP button to mechanically trip the circuit breaker Trip reset and switch circuit breaker ON several times If mechanism does not reset each time the circuit breaker is tripped replace the circuit breaker Check base cover and operating handle for cracks chipping and discoloration C...

Страница 6: ...tting Number Setting A 0 0 5 A 0 9 B 12 0 B 60 0 C 15 0 C 75 0 D 3 18 0 D 30 90 0 E 21 0 E 105 0 F 24 0 F 120 0 G 27 0 G 135 0 H 30 0 H 150 0 A 21 0 0 9 A B 28 0 B 120 0 C 35 0 C 150 0 D 7 42 0 D 30 180 0 E 49 0 E 210 0 F 56 0 F 240 0 G 63 0 G 270 0 H 70 0 H 300 0 A 0 6 6 A 0 5 4 B 60 0 B 97 0 C 75 0 C 112 5 D 15 90 0 D 50 128 0 E 105 0 E 143 5 F 120 0 F 159 0 G 135 0 G 174 5 H 150 0 H 190 0 A 40 ...

Страница 7: ...0MM 490 0 F 560 0 G 630 0 H 700 0 0 0 5 1 A B 200 0 C 250 0 D 100 E2Fl OOKM 300 0 E E2FMl OOKM 350 0 F 420 0 G 450 0 H 500 0 0 0 0 3 A B 400 0 C 500 0 D 100 E2Fl OORM 600 0 E E2FMlOORM 700 0 F 800 0 G 900 0 H 1000 0 0 0 5 4 A B 600 0 C 750 0 D 150 EZFI 50TM 900 0 E EZFM150TM 1050 0 F 1200 0 G 1350 0 H 1500 0 TABLE 3 1 MCP TRIP SETTINGS CONT Cam Continuous MCP MCP Setting Amps Catalog Trip Number S...

Страница 8: ... consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equi...