E02A INTEGRATED RACK TYPE AIR CONDITIONER
UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com
•
Alarm output (option)e:
The unit provides alarm output dry contact. If there is no alarm, the dry contact is close. When there is alarm,
the dry contact will open. Contact capacity: resistive load 5A@30VDC/5A@250VAC.
3.3 Power-on steps
Firstly make sure the AC voltage is in accordance with the standard, and then close the power input switch. 30s
later the internal cycle fan of the unit will be started. After delay time about 3min, the unit select operation mode
according to the unit’s.