4 Commissioning
4.6 Operation
DX-NET-PROFINET-2
09/13 MN04012007Z-EN
www.eaton.com
35
4.6.2 Acyclic data access
DX-NET-PROFINET-2 allows for acyclic communications.
This requires certain settings so that it will be possible to write parameter
values to the variable frequency drive and read them from it.
Follow the steps below:
▶
In IPconfig, right-click on the line and select the
Open Web-Interface
option from the context menu.
▶
Then click on
Parameter data
. (The following screenshot shows an
excerpt.)
▶
Now enter the parameter values you want in the
Value
column.
▶
Finally, click on
Set
in order to transfer the values to the variable
frequency drive.