Replacement Parts

ITEMS

DESCRIPTION

EATON STYLE NUMBER

SPRING RELEASE COILS / SHUNT TRIPS

24Vdc

48Vdc

125Vdc / 120Vac

250Vdc / 240Vac

94C9525G16

94C9525G17

94C9525G18

94C9525G19

Component Replacement

otee:

N

Removal of shunt trip coil on a 29WR element.

 WARNING

VERIFY CIRCUIT BREAKER IS OPEN, CLOSING SPRINGS ARE  

  DISCHARGED AND CONTROL POWER IS DISCONNECTED.

REFERENCE: THE SPRING RELEASE COIL IS THE COIL ON THE 

LEFT SIDE, LOOKING INTO THE CIRCUIT BREAKER, WITH 

THE GREEN “PUSH TO CLOSE” LABEL 

Replacing The Spring Release Coil (Close Coil)

Cut 4 to 6 tie wraps that hold the wires that go between 

the close and trip coils to the terminal block in the lower 

right side of the mechanism.
Remove two wires from TB1 and TB2 and pull the wires 

through the support bracket toward the close coil.
Remove the 5/16 x 3 ¼ in. hex head bolt, lock washer 

and spacer that hold the coil in place. Be careful to 

capture the two fiber insulating washers behind the coil.

otee:

N

The 5/16 x 3 ¼ in. bolt is made of silicon bronze for  

magnetic purposes and must never be replaced with a steel bolt.

Slide the coil out of its bracket (to the left) and feed the 

wires through. Remove the metal core from the center 

of the coil.
Install new wire markers on the new coil leads. Polarity is 

not an issue.
Insert the metal core into the center of the new coil.
Fish the coil wires through the cut out and slide coil into 

the bracket while gently pulling the leads.
Insert the bolt, lock washer and spacer and place the 

two fiber washers on the bolt when it exits the coil 

(one at a time and screw bolt into washers). Screw bolt 

into threaded insert in bracket and tighten. Do not over 

tighten!
Fish wires through to terminal block. Connect wires to 

terminal block TB1 and TB2. Install tie wraps to hold wire 

bundle.
Mechanically and electrically test the circuit breaker and 

hipot the secondary wiring.

 WARNING

VERIFY CIRCUIT BREAKER IS OPEN, CLOSING SPRINGS ARE  

  DISCHARGED AND CONTROL POWER IS DISCONNECTED. 

REFERENCE: THE SHUNT TRIP COIL IS THE COIL ON THE 

RIGHT SIDE, LOOKING INTO THE CIRCUIT BREAKER, WITH 

THE RED “PUSH TO OPEN” LABEL 

Replacing The Shunt Trip Coil

Cut 4 to 6 tie wraps that hold the wires that go between 

the close and trip coils to the terminal block in the lower 

right side of the mechanism.
Remove two wires from TB3 and TB4 and pull the wires 

through the support bracket toward the close coil.
Remove the 5/16 x 3-¼ in. hex head bolt, lock washer 

and spacer that hold the coil in place. Be careful to 

capture the two fiber insulating washers behind the  

coil. 

otee:

N

The 5/16 x 3-¼ in. bolt is made of silicon bronze for  

magnetic purposes and must never be replaced with a steel bolt. 

Slide the coil out of its bracket (to the right). Remove the 

metal core from the center of the coil.
Install new wire markers on the new coil leads. Polarity is 

not an issue.
Insert the metal core into the center of the new coil.
Slide coil into the bracket.
Insert the bolt, lock washer and spacer and place the 

two fiber washers on the bolt when it exits the coil  

(one at a time and screw bolt into washers). Screw bolt 

into threaded insert in bracket and tighten. Do not over 

tighten!
Fish wires through to terminal block. Connect wires to 

terminal block TB3 and TB4. Install tie wraps to hold wire 

bundle.
Mechanically and electrically test the circuit breaker and 

hipot the secondary wiring.

9

EATON

   |   Visual Instruction Booklet Essentials   |   DST-2-VR - 18WR Element   |   May 2017  

Содержание DST-2-VR

Страница 1: ...For VR Series Circuit Breakers This is a user interactive supplemental booklet This material is intended to enhance the technical information included in the instruction booklet for the vacuum replace...

Страница 2: ...on and maintenance of medium voltage circuits and equipment should be permitted to work on these circuit breakers Always remove the circuit breaker from the enclosure before performing any maintenance...

Страница 3: ...m Interrupter Assembly Each interrupter is assembled at the factory as a unit to assure correct dimensional relationships between working components The interrupter assembly consists of a vacuum inter...

Страница 4: ...ENTIAL TESTS ARE NOT RECOMMENDED BY EATON DO NOT APPLY DC AT ANY LEVEL TO VR SERIES POWER CIRCUIT BREAKERS With the circuit breaker open and securely sitting on the floor connect all top front primary...

Страница 5: ...L BELOW MAXIMUM PERMITTED BY STANDARDS HOWEVER AS A PRECAUTIONARY MEASURE AGAINST POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE AND OR BELOW NORMAL CONTACT SPACING IT IS RECOMMENDED TH...

Страница 6: ...BOTTOM terminal of the phase being tested 8 Press the TEST button on the DLRO Once the TEST button is pressed 100A dc will flow through the phase being tested If the circuit breaker is not closed the...

Страница 7: ...ent speed for interruption Stroke is the gap between fixed and moving contacts of a vacuum interrupter with the circuit breaker open The circuit breaker mechanism provides a fixed amount of motion to...

Страница 8: ...d the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is def...

Страница 9: ...bracket and tighten Do not over tighten Fish wires through to terminal block Connect wires to terminal block TB1 and TB2 Install tie wraps to hold wire bundle Mechanically and electrically test the c...

Страница 10: ...k the threads Remove the two screws on the right hand motor support plate using a 9 64in Allen wrench Remove the motor plate from the side sheet for the 5kV circuit breaker Remove the motor Verify the...

Страница 11: ...afety Precautions Read and understand the instruction manual for specific instructions before attempting any maintenance repair or testing on the circuit breaker The user is cautioned to observe all r...

Страница 12: ...VR Series Circuit Breaker DST 2 5 VR 350 2000A 12 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Страница 13: ...VR Series Circuit Breaker DST 2 15 VR 1200A 13 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Страница 14: ...nts and engineering services Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges Eaton is a power management company with 2015 sales...

Отзывы: