background image

8

Instruction Leaflet 

IL29C614F

Effective December 2011

Instructions for The Digitrip RMS 310 3-Pole and 

4-Pole Trip Unit Installation and Operation with 

K-Frame Series C Circuit Breakers

EATON CORPORATION

 www.eaton.com

3.3.3  ACCESSORY INSTALLATION WITH GROUND

FAULT TRIP UNITS

If an accessory other than the auxiliary switch supplied with

the trip unit is to be used, install the accessory by using the

appropriate instruction leaflet listed in Section 8.2. 

See wiring instructions below for special restric-

tions on accessory wiring for ground fault breakers.

Then install the ground fault alarm and neutral cur-

rent sensor connector printed circuit board as

described above. 

LEADS COULD BE DAMAGED IF IN CONTACT WITH

MOVING PARTS. ACCESSORY WIRES SHOULD BE

FORMED AND ROUTED TO CLEAR ALL MOVING

PARTS.

When the appropriate accessory and the connector board

are installed there are up to three sets of leads to be routed: 

1. Two leads (white and grey) for the neutral current 

sensor,

2. Two leads (yellow and green) for the ground fault alarm

relay, and 

3. Three leads (red, blue and black) for the accessory

switch.

If all three sets of connections are required, it is not pos-

sible to have leads exiting breaker on the opposite side.

For rear existing leads (preferred), thread the leads

through the wiring troughs in the side of the circuit break-

er case. For side existing leads, use the slots in the side

of the case. Use the trough or slot farthest from the trip

unit for the auxiliary switch leads(red, blue and black),

the center trough or slot for the neutral current sensor

leads (white and grey), and the trough or slot closest to

the trip unit for the alarm leads (yellow and green). 

If only one or two sets of leads are required, they can be

routed to the side or rear as above, or one set can be

fed to the opposite side through the rear wiring trough.

This set of leads should first be threaded through the

center wiring trough in the side of the case, then through

the rear wiring trough. Any other leads to be brought out

should then be threaded through the wiring trough clos-

est to the trip unit. 

Finish installation of the ground fault trip unit by follow-

ing the instructions in Section 3.5.

3.4  3-POLE (NON-GROUND FAULT) TRIP UNIT

INSTALLATION

Position trip unit in base. Make sure latch bracket pin is

properly seated in slots in side plates (see Figure 

6

).  If

necessary, move latch toward load end of circuit break-

er to seat trip unit. 

DO NOT EXCEED A TORQUE OF 6 TO 8 LB.-FT 

(8 TO 10 NM). EXCESSIVE TORQUING WILL SHEAR

SCREWS.

FAILURE TO APPLY THE REQUIRED TORQUE MAY

LEAD TO EXCESSIVE HEATING AND CAUSE NUI-

SANCE TRIPPING OF THE CIRCUIT BREAKER. 

Screw in and tighten three trip unit retaining screws

(center first). Torque to 6 to 8 lb.-ft (8 to 10 Nm) (see

Figure

6

).

Install accessory(ies), if required, using the appropriate

instruction leaflet listed in Section 8.2. 

3.5  FINAL INSTALLATION INSTRUCTIONS (ALL

TRIP UNITS) 

Install conductor barriers in slots in base (see Figure 

2

).

DAMAGED THREADS CAN RESULT IN IMPROPER

CIRCUIT BREAKER COVER RETENTION. WHEN

REMOVING OR REINSTALLING, THREAD FORMING

SCREWS TRY TO RE-FORM THE THREADS IN THE

CIRCUIT BREAKER BASE. CARE SHOULD BE

TAKEN EVERY TIME A THREAD FORMING SCREW

IS USED TO ENSURE THE SCREW STARTS IN THE

ORIGINAL THREADS.

When the trip unit is installed in a new circuit break-

er frame, the remaining cover mounting hard ware is

supplied in a plastic bag with the frame. 

NOTICE

!

CAUTION

!

CAUTION

!

CAUTION

NOTICE

Содержание Digitrip RMS 310

Страница 1: ...of Operation 11 5 0 Protection Settings 11 6 0 Testing 12 7 0 Rating Plug 15 8 0 References 15 Effective December 2011 Supersedes IL29C614E 02 09 Instruction Leaflet IL29C614F Instructions for The Di...

Страница 2: ...odes and procedures The recommendations and information contained herein are based on Eaton experience and judgment but should not be considered to be all inclusive or covering every application or ci...

Страница 3: ...Short Delay Time Ground Fault Pick up KESxxxxLSlG Ground Fault Time 2 0 UL LISTED DEVICES The Digitrip RMS 310 Trip Unit is listed in accordance with Underwriters Laboratories Inc Standard UL489 unde...

Страница 4: ...p unit conductor holes at this time If preferred a magnetic screwdriver may be used to position the screws when the trip unit is in the base Make sure shunt plates are centered over shunt plate insert...

Страница 5: ...FT 8 TO 10 N M EXCESSIVE TORQUING WILL SHEAR SCREWS FAILURE TO APPLY THE REQUIRED TORQUE MAY LEAD TO EXCESSIVE HEATING AND CAUSE NUI SANCE TRIPPING OF THE CIRCUIT BREAKER Screw in and tighten three tr...

Страница 6: ...rce ground or zero sequence ground fault sensing methods If the system neutral is grounded but no phase to neutral loads are used the neutral current sensor is not necessary In that case the white and...

Страница 7: ...E NUI SANCE TRIPPING OF THE CIRCUIT BREAKER Screw in and tighten three trip unit retaining screws center first Torque to 6 to 8 lb ft 8 to 10 Nm see Figure 6 To install the ground fault alarm and neut...

Страница 8: ...o the trip unit for the alarm leads yellow and green If only one or two sets of leads are required they can be routed to the side or rear as above or one set can be fed to the opposite side through th...

Страница 9: ...to position depress the Push to Trip button with a small screwdriver and turn it clockwise one quar ter of a turn until the arrow points to ENGAGED If an adjustable rating plug is used four continuous...

Страница 10: ...elay Trip Current and Short Delay Trip Time Adjustment and Curve Details Current In Short Delay Pick up Multiples of Rated Current Time 5 6 4 3 2 2 8 7 8 300 200 100 I I 100 200 300 Figure 12 3 Ground...

Страница 11: ...re program then determines whether to initiate protec tion functions including tripping the breaker through the flux transfer shunt trip device in the circuit breaker A green status light indicates th...

Страница 12: ...e 1 2 These ampere values are always the same no matter what rating plug is installed in the circuit breaker Available on Catalog Nos KES3xxxLSG and LSIG 5 6 GROUND FAULT TIME SETTINGS The ground faul...

Страница 13: ...MS 310 Trip Units derive their operating power from the phase currents and not from the neutral current passing current through the neutral sensor will not properly test the ground fault feature Figur...

Страница 14: ...ULT TRIP UNIT ANY TEMPORARY CONNECTION MADE FOR THE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTORED TO PROPER OPERATING CONDITIONS BEFORE RETURNING THE BREAKER TO SERVICE CAUTION Polarity Marks Current...

Страница 15: ...mary cur rent carrying conductors used with the breaker must be sized to correspond with the maximum setting of the rat ing plug in accordance with National Electrical Code requirements The Long Delay...

Страница 16: ...Lockout Switch and Terminal Block GFAU Ground Fault Alarm Unit Trip Unit Functions 3 POLE 4 POLE KES3125LS KES3125LSI KES3125LSG KES3125LSIG KES4400LS KES4400LSI KES4400LSE KES4400LSIE KES3250LS KES32...

Страница 17: ...In 250A 125A 150A 200A 250A In 125A 160A 225A 250A In 400A 200A 250A 300A 400A In 200A 250A 315A 400A In 250A 300A 350A 400A In Short Delay Pick up In multiples of installed rating plug amperes Adjust...

Страница 18: ...on Leaflet IL29C614F Effective December 2011 Instructions forThe Digitrip RMS 310 3 Pole and 4 PoleTrip Unit Installation and Operation with K Frame Series C Circuit Breakers EATON CORPORATION www eat...

Страница 19: ...on Leaflet IL29C614F Effective December 2011 Instructions forThe Digitrip RMS 310 3 Pole and 4 PoleTrip Unit Installation and Operation with K Frame Series C Circuit Breakers EATON CORPORATION www eat...

Страница 20: ...information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eat...

Отзывы: