EATON CORPORATION www.eaton.com
11
Instruction Leaflet IL 33-LGH-3
Effective September 2010
Digitrip Retrofit System for the ITE
LG-3000 (Frameless) Circuit Breaker
F. Mount the Trip Assembly to the Breaker Trip
Bar, as shown, using the (2) .250-20 x 1.00"
bolts, (2) lock washers, and (2) flat washers
supplied.
G. Remove and save the two (2) bolts and
washers from the left side of the Breaker
Cross Bar.
H. Remove and save the two (2) nuts, two (2)
washers, and the spring from the Reset Shaft.
While holding the brass spacer in place on
the Shaft, insert the Reset Shaft into the cut-out
in the DTA Reset Arm. Reinstall the original
hardware on the Reset Shaft in the following
order: washer, spring, adjusting nut, and
lock nut.
I.
Align the holes in the Reset Assembly Mounting
Bracket with the holes in the Breaker Cross Bar.
J. Mount the Reset Assembly to the Breaker
Cross Bar, as shown, using the original
hardware removed in Step 6-G.
K. Connect the wire from the DTA Extension
Harness marked with the “+” to the “+” terminal
and the unmarked wire to the other terminal on
the 2-Point Terminal Block mounted to the DTA
Assembly.