12
Table B-8. Format of Assembly Instance #156 – Motor Alarm Counts.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status
32
2
1
StatusByte
33
2
2
GndFaultAlrmsCnt 113 2
3
I2TalrmsCnt
114
2
4
JamAlrmsCnt 115
2
5
UndrLdAlrmsCnt
116
2
6
PhsUnbalAlrmsCnt 117 2
7
WindTempAlrmsCnt
118
2
8
MotrBrngAlrmsCnt 119 2
9
LoadBrngAlrmsCnt
120
2
10
AuxTempAlrmsCnt 121 2
11
StrtPerTAlrmsCnt
122
2
12
RtdFailAlrmsCnt 123 2
13
URtdFailAlrmsCnt
124
2
14
AcLastResetDateM 125 2
15
AcLastResetDateD
126
2
16
AcLastResetDateY 127 2
17
AcLastResetTimeH
128
2
18
AcLastResetTimeM 129 2
19
AcLastResetTimeS
130
2
Table B-9. Format of Assembly Instance #157 – Flags.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status
32
2
1
StatusByte
33
2
2
FlagsStatus 37
2
3
FlagsReason
38
2
4
FlagsBitsB15B00 131 2
5
FlagsBitsB31B16
132
2
6
FlagsBitsB47B32 133 2
7
FlagsBitsB63B48
134
2
Consumed Assembly Instances
There is one consuming assembly supported for the MP-3000 as indicated in the following table.
Table B-10. Consumed Assembly Instances.
Inst #
Assembly Name
Number of Data Bytes
Access
100
SlaveActions
2
Set
101
Reserved
-
Set
102
Reserved - Set
103
Reserved
-
Set
Table B-11. Format of Assembly Instance #100 – Slave Actions.
Word #
Member
Parameter Inst #
Data Bytes
0
SlaveActions 39
2