Instruction Leaflet 

IL159026EN

Effective February 2022

Replacement instructions   

for CX with CX Plus controller 

  

EATON

 www.eaton.com

Table 1.  Default settings

Menu Function

Default

Customer  

settings

100 

Quick start setup

Un 

Nominal voltage (phase-phase) 

208 V / 240 V /  

480 V / 600 V

Ct

CT-Ratio

600 (corresponds to 

3000:5 CT ratio)

Pt

VT-ratio

1.7 (240 V unit)  

3.7 (480 V unit)  

4.7 (600 V unit)

Ai

Start automatic initializing

N

PFC

Start/Stop/Hold PF-control

On

CP1

Target-PF 1

0.95i

St

Switching time delay

60 s

Out 

Type of each step (1, 2, 3…12) 

Auto (for each step 

installed in unit), 

Fixed Off (for unused 

controller outputs)

200 

Setup measuring system

201 

Nominal voltage (phase-phase) 

208 V / 240 V /  

480 V / 600 V

202 

CT-ratio 

600 (corresponds to 

3000:5 CT ratio)

203 

VT-ratio 

1.7 (240 V unit)

3.7 (480 V unit)

4.7 (600 V unit)

204

Tolerance nominal voltage

20%

205

Voltage measuring

Y = L–L

206

Phase-offset

90

207

Start automatic initializing

N

208

Synchronization to frequency

60 (60 Hz unit)

209

Temperature offset

0 °C

300 

Setup control system

301

Switching threshold

55%

302

Target-PF 1

0.95i

303

Target-PF 2

0.95i

304

Target-PF 2 at KW-export

N

305

Switching time delay

60 s

306

Switching time delay for fine control

10 s

307 

Fine control active 

N (for units with 

equal stage sizes), 

Y (for units with 

multiple stage sizes)

308

Automatic Stage detection

N

309

Block defective Capacitors

N

310

Start/Stop/Hold PF-control

On

311

Control algorithm

1

312

Reactive-power offset

0

313

Asymmetrical switching time delay

1

314

Switch-off capacitors in leading 

condition

N

315

Distribute sw. operations

N

316

Detect faulty stages

Y

400

Setup capacitor database

401 

Discharge time

60 s

402 

Capacitor size: step 1…max. 12

Varies (see equipment 

drawings for step size, 

typically 25, 50, or 

100 kvar capacitive)

Menu Function

Default

Customer  

settings

400

Setup capacitor database, 

continued

403 

Type of exit: step 1…max. 12

Auto (for each step 

installed in unit), 

Fixed Off (for unused 

controller outputs)

404 

Switching operations: step 1…max. 12 0

405

Operations hours counter:  

step 1…max. 12

0 h

406

Fan relay as stage output

N

500 

Setup alarm system

501 

Reset alarms manually

N

502 

THD-U threshold

6%

503 

Disconnect capacitors when THD >

N

504 

THD alarm delay

120 s

505 

Stop control if I=0

N

506 

Service alarm

N

507 

Max. operations per step

262 k

508 

Max. operation hours of BLR-ACX-V

65.5 k

509 

Max. operation hours per step

65.5 k

510 

THD-I threshold

20%

511 

Digital input logic

Y

512 

Temp. threshold level 1  

(fan control, type of exit: AL)

40 °C

513

Temp. threshold level 2,  

disconnect capacitors

55 °C

514

Control alarm (target cannot be reached) Y

515 

Faulty stages alarm

Y

516 

Stage power loss alarm

Y

517 

Flashing display

N

518

Digital input function

CP2

519

I-Low alarm suppr.

Y

520

Switch off active stages if digital 

input alarm

N

521

I-Low alarm

Y

522

I-High alarm delay

10 s

523

Switch-off interval

60 s

600 

Reset

601

Reset to default values

N

602

Reset capacitor database to default

N

603

Reset operation hours

N

604

Reset average PF

N

605

Reset max. temperature

N

606

Reset alarm

N

607

Info firmware

608

Change password

242

609

Restart first setup

N

700 

Modbus

Baud rate

19.2 k

Parity and stop bits

EVEN

Slave address

1

800

System

801

Backlight during commissioning mode

N

802

Backlight delay time

0.25 h