Page 2
.
Effective.June.2007
RS-485 PONI
66A2070 Rev. B
Figure2: Mounting to an IQ Analyzer
Mount the RS-485 PONI with the label facing up, the LEDs
on the left, and the ribbon cable on the right.
Connect the ribbon cable from the RS-485 PONI to the
receptacle of the IQ Device, shown in Figure 3 (below), and
firmly tighten the screws on the plug lock assembly.
Refer to Figure 2 for dimensions.
Ribbon Cable
Connector
Plug Lock
Assembly
Figure 3: Attaching the Cable to the Plug Lock Assembly
A fuse change is needed on an IQ Analyzer 6000/6200
series, style style #’s 2D82302Gxx, and on IQ DP-4000’s,
style #’s 4D3Gxx. While the power to the IQ device is
disconnected, replace the ¼-Amp fuse with the ½-Amp
fuse.provided .
Restore power to the IQ device. New IQ Analyzer
6400/6600 series style #’s 66D2045Gxx, and IQ DP-4000’s,
style #’s 66D2040Gxx do not have external power supply
fuses. These new style meters do not require the ½-Amp
fuse.included .
3b. Mounting to the IQ DP-4000 or IQ Data Plus II
Mounting to the IQ DP-4000 or to the IQ Data Plus II is
the same as for the IQ Analyzer. Refer to IQ Analyzer
instructions (in 3a) to complete the installation. Refer to
Figure 4 below for dimensions.
Figure 4: Mounting to a DP-4000
3c. Mounting to an MP-3000
To mount a RS-485 PONI onto the MP-3000, use the
U-shaped mounting bracket and #6 32 x /4" pan head
screws supplied with the MP-3000. Use this bracket only
when a URTD is not mounted on the MP-3000. If a URTD
is mounted on the back of the MP-3000, the RS-485 PONI
can piggy-back directly onto the URTD. The machine screws
supplied with the RS-485 PONI are then used to screw into
the molded plastic mounting-holes of the URTD. Refer to the
MP-3000 IL 7562x for additional information. To order this
mounting bracket, use Part Number 7066C H0.
Figure 5: Mounting to an MP-3000