I.B. 8295A61H03
Page 40
Effective 7/97
Figure 7-5 Wipe Indication Procedure (Performed Only with Breaker Closed)
Any part of Red or Gray Indicator Visible
— “Wipe” Satisfactory
Red or Gray Indicator Not Visible
— “Wipe” Unsatisfactory
Any part of “T” Shape Indicator Visible
— “Wipe” Satisfactory
“T” Shape Indicator Not Visible
— “Wipe” Unsatisfactory
Any part of Indicator Visible
— “Wipe” Satisfactory
Indicator Not Visible
— “Wipe” Unsatisfactory
WHITE CONTACT SPRINGS
BLUE OR RED
CONTACT SPRINGS
ORANGE OR BLACK
CONTACT SPRINGS