manualshive.com logo in svg
background image

I.B. 3A74792H04

Page 5

Effective 7/97

SECTION 3: RECEIVING, HANDLING AND
STORAGE

3-1  GENERAL

Type VCP-W Vacuum Circuit Breakers are subjected to
complete factory production tests in accordance with
ANSI C37.09 and inspection before being packed. They
are shipped in packages designed to provide maximum
protection to the equipment during shipment and stor-
age and at the same time to provide convenient han-
dling. Tools and accessories, such as the maintenance
tool, are shipped separately.

3-2  RECEIVING

If the circuit breaker is not to be used immediately but is
to be placed in storage, maximum protection can be
obtained by keeping it packed as shipped.

Upon receipt of the equipment, inspect the containers
for any signs of damage or rough handling. Open the
containers carefully to avoid any damage to the con-
tents. Use a nail puller rather than a crow bar when
required. When opening the containers, be careful to
save any loose items or hardware that may be other-
wise discarded with the packing material. Check the
contents of each package against the packing list.

Examine the circuit breaker for any signs of shipping
damage such as broken, missing or loose hardware,
damaged or deformed insulation and other components.
File claims immediately with the carrier if damage or loss
is detected and notify the nearest Cutler-Hammer Office.

The VCP-W 38kV shipping container and pallet were
specifically designed to facilitate removal of the cir-
cuit breaker from its pallet and container. Before
proceeding, installation personnel should be famil-
iar with the procedures outlined in Paragraph 3-3
entitled “Handling.”

3-3  HANDLING

DO NOT USE ANY LIFTING DEVICE AS A PLAT-
FORM FOR PERFORMING MAINTENANCE, REPAIR
OR ADJUSTMENT OF THE CIRCUIT BREAKER OR

FOR OPENING, CLOSING THE CONTACTS OR
CHARGING THE SPRINGS. THE CIRCUIT BREAKER
MAY SLIP OR FALL CAUSING SEVERE PERSONAL
INJURY. ALWAYS PERFORM MAINTENANCE,
REPAIR AND ADJUSTMENTS ON A SOLID WORK
SURFACE CAPABLE OF SUPPORTING THE CIR-
CUIT BREAKER.

VCP-W 38kV Vacuum Circuit Breakers are shipped
mounted to a skid specially designed to facilitate
removal of the breaker. Refer to Figures 3-1 and 3-2
and proceed with the following steps:

AFTER REMOVING THE BRACKETS USED TO
HOLD THE CIRCUIT BREAKER SECURELY TO THE
SHIPPING SKID AND ALL DURING THE PROCESS
OF MOVING THE CIRCUIT BREAKER OFF OF THE
SHIPPING SKID AND DOWN THE RAMP TO THE
FLOOR, TAKE SPECIAL PRECAUTIONS TO INSURE
THAT THE CIRCUIT BREAKER IS MOVED SLOWLY

Figure 3-1  Circuit Breaker Shown Mounted with Ramp
Still in Shipping Position

!

WARNING

!

WARNING

NOTICE

Содержание Cutler-Hammer VCP-W

Страница 1: ...I B 3A74792H04 Effective 7 97 Cutler Hammer Instructions for Installation Operation and Maintenance of Type VCP W 38kV Vacuum Circuit Breakers...

Страница 2: ......

Страница 3: ...RY OR PROPERTY DAMAGE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING ANY UNPACKING ASSEM BLY OPERATION OR MAINTENANCE OF THE CIR CUIT BREAKERS INSTALLATION OR MAINTENANCE SHOULD BE ATTEMPTED...

Страница 4: ...CTION 4 INITIAL INSPECTION AND INSTALLATION 4 1 Introduction 12 4 2 Manual Operation Check 12 4 3 Vacuum Interrupter Integrity 12 4 4 Insulation 12 4 5 Contact Erosion and Wipe 12 4 6 Primary Circuit...

Страница 5: ...INTENANCE AND TROUBLESHOOTING 6 1 Introduction 26 6 2 Frequency of Inspection and Maintenance 26 6 2 1 Qualified Personnel 26 6 2 2 Helpful Tools and Accessory Items 26 6 2 3 General Torque Guidelines...

Страница 6: ...Representation of Arc Interruption 17 5 4 Closing Cam and Trip Linkage 19 5 5 Charging Schematic 21 5 6 Typical 38kV VCP W DC and AC Control Schematics 22 5 7 Secondary Circuit Breaker Plug Shown Moun...

Страница 7: ...S PART OF THE PROCEDURAL STEPS IN THIS DOCU MENT ARE FOR PERSONNEL SAFETY AND PRO TECTION OF EQUIPMENT FROM DAMAGE AN EXAMPLE OF A TYPICAL WARNING LABEL HEAD ING IS SHOWN ABOVE IN REVERSE TYPE TO FAMI...

Страница 8: ...rrent 1 Minute Time Rated Current Short Carrying Circuit Capability Current E K I Y kV Class kV rms kV rms kV Peak Amperes kA rms Cycles Seconds kV Peak s kA Peak Amperes kA Amperes rms Amperes rms rm...

Страница 9: ...SAME LENGTH AS 2000A CONDUCTORS 35 7 908 REF 17 8 454 11 8 300 11 8 300 64 6 1641 6 14 11 1 283 REF 1 0 26 2 9 75 35 7 908 17 9 454 16 4 417 16 4 417 12 4 314 2 5 9 88 251 5 4 137 1 7 44 CONTACT EROS...

Страница 10: ...coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death personal injury or property damage Do not work on a closed circuit breaker or a breaker wit...

Страница 11: ...deformed insulation and other components File claims immediately with the carrier if damage or loss is detected and notify the nearest Cutler Hammer Office The VCP W 38kV shipping container and palle...

Страница 12: ...to be placed in storage maxi mum protection can be obtained by keeping it packed as shipped Before placing it in storage checks should be made to make sure that the circuit breaker is free from shipp...

Страница 13: ...ear the floor Indoor storage should be in a building with sufficient heat and air circulation to prevent condensation If the building is not heated the same general rule for heat as for outdoor storag...

Страница 14: ...Effective 7 97 Figure 3 4 Front View VCP W 38kV Vacuum Circuit Breaker Front Cover Lift Pull Handle Contact Erosion Indicator Flags Circuit Breaker Wheel Secondary Contact Block Alignment Rollers 3 4...

Страница 15: ...10 9 11 12 13 Shock Absorber Shunt Trip Assembly Spring Release Close Coil Assembly Closing Cam Open Close Indicator Operations Counter L H Closing Spring Motor Cutoff Switch R H Closing Spring Openi...

Страница 16: ...ive 7 97 Figure 3 6 Rear View VCP W 38kV Vacuum Circuit Breaker Pole Unit Primary Disconnect Insulation Shroud Opening to View Contact Erosion Mark Circuit Breaker Wheel Alignment Rollers TOC Operator...

Страница 17: ...ve 7 97 Figure 3 7 Typical VCP W 38kV Escutcheon Manual Charge Socket Spring Charged Discharged Indicator Rating Nameplate Manual Open Button Manual Close Button Open Close Indicator Operations Counte...

Страница 18: ...ged If the springs are to be charged on a closed circuit breaker no click is heard at the end of charging operation Discontinue charging and remove the maintenance tool as soon as Charged flag is full...

Страница 19: ...he TEST position To engage the secondary contacts grasp the structure mounted secondary disconnect cage handle located below the left side of the circuit breaker and pull it for ward as far as possibl...

Страница 20: ...lready closed Figure 5 5 On a closed circuit breaker the interlock lever moves toward the rear In this position the movement of the spring release clapper does not lift the lever and thus the spring r...

Страница 21: ...and structural assembly manual are intended to verify safe and proper operation If observed conditions are not as described contact Cutler Hammer for assistance Figure 4 2 Type VCP W Circuit Breaker...

Страница 22: ...control circuits with all terminals being of the screw type This section describes the overall operation of the circuit breaker as well as the function and operation of all major sub assemblies and or...

Страница 23: ...d fast Figure 5 3 In the closed position current flows through the interrupter When the contacts are opened the arc is drawn between the contact surfaces It is moved rapidly around the slotted contact...

Страница 24: ...in the design of all Cutler Hammer vacuum circuit breakers in order to eliminate the need for field adjustments of wipe or stroke THERE IS NO PROVISION FOR IN SERVICE ADJUSTMENTS OF CONTACT WIPE AND S...

Страница 25: ...pring charged Figure 5 4b Breaker open and closing spring charged Figure 5 4a Breaker open and closing spring discharged Figure 5 4c Breaker closed and closing spring discharged 9 5 6 4 8 7 3 10 2 1 C...

Страница 26: ...ntacts are completely enclosed in the vacuum interrupter and not adjustable in any way a Slow Close capability is not provided with VCP W cir cuit breakers 5 3 4 TRIPPING OPERATION When the trip D sha...

Страница 27: ...Pole Shaft Anti Close Interlock Spring Release Close Latch Spring Crank Closing Spring Closing Spring Fixed End Spring Release Close Coil Figure 5 5 Charging Schematic 9 11 5 6 4 8 7 3 10 2 1 12 Cam...

Страница 28: ...TION IS CHOSEN AND MAKE THE APPROPRIATE CONNECTIONS AUXILIARY SWITCH 2 OPTIONAL a b b a b a b a b a U24 U19 U20 U21 U22 U23 U16 U17 U18 U15 U1 U9 U8 U7 U6 U5 U4 U3 U2 U10 OPTIONS 6 M WL SPRING CHARGED...

Страница 29: ...e across the trip coil is greater than 30 but less than 60 of the voltage rating of its trip coil The circuit breaker can be closed as long as the voltage to the trip coil is maintained at 85 or above...

Страница 30: ...s con cerning the use of the levering mechanism to move the circuit breaker into and out of the CONNECTED position within the assembly structure 5 7 OPERATIONS COUNTER All circuit breakers are equippe...

Страница 31: ...ective 7 97 2 3 7 8 4 6 1 5 2 5 6 4 8 7 3 2 1 Moving Clapper Stationary Yoke UV Trip Device Coil Extension Springs Trip D Shaft Lever Slotted Link Pole Shaft Lever Reset Lever Figure 5 8 Undervoltage...

Страница 32: ...tain a dated permanent record of all inspections maintenance performed actions taken observations made and measurements taken Not only will this provide valuable historical information it can help to...

Страница 33: ...e individual performing the work OVER TORQUING CAN CAUSE PERMANENT DAM AGE WHILE UNDER TORQUING WILL NOT PRO VIDE THE PROPER CLAMPING FORCE AND MAY EVENTUALLY WORK LOOSE Table 6 1 Torque Guidelines Bo...

Страница 34: ...I B 3A74792H04 Page 28 Effective 7 97 Figure 6 1 Lubrication Points Apply one drop of light machine oil such as Mobil One at locations shown...

Страница 35: ...with integrity check as If integrity check is not satisfactory described in Paragraph 6 4 replace pole unit assembly Primary Disconnects No burning or damage Visual Check Replace if burned damaged or...

Страница 36: ...ical charge that may be retained To avoid any ambi guity in the ac high potential test due to leakage or dis placement capacitive current the test unit should have sufficient volt ampere capacity It i...

Страница 37: ...tage is 60kV rms Conduct the test as follows Close the circuit breaker Connect the high potential lead of the test machine to one of the poles of the circuit breaker Connect the remaining poles and ci...

Страница 38: ...ly and electrically Check the closing and opening times to verify that they are in accordance with the limits in Table 5 1 6 11 LUBRICATION All parts that require lubrication have been lubricated duri...

Страница 39: ...ease 53701QB or equiv alent Rated Continuous Current amperes 600 1200 1600 2000 Resistance microohms 92 90 88 72 Table 6 3 Typical Resistance Measurements 6 12 TROUBLESHOOTING CHART Continued Next Pag...

Страница 40: ...act open or burned or relay picks up Close Coil Open or burned Latch Check Switch Contact open bad switch or trip bar not reset Auxiliary Switch b contact open or burned Motor Cut off Contacts open or...

Страница 41: ...aking poor or burned Trip Coil Burned or open Terminals and Connections Poor or burned or open Trip Mechanism Trip Clapper Jammed Trip Sound Trip Mechanism Trip Bar Trip Latch But No Trip Jammed Pole...

Страница 42: ...ing information and shop order number b Describe the item give the style number and specify the quantity required c Specify the voltage for electrical components d Specify the method of shipping desir...

Страница 43: ...3 12 380 32 2000A 31 5kA 3A74861H01 3 13 380 1500 600A 35kA 3A74865H01 3 14 380 1500 1200A 35kA 3A74866H01 3 15 380 1500 1600A 35kA 3A74867H01 3 16 380 1500 2000A 35kA 3A74868H01 3 Charging Motor 17...

Страница 44: ...7H05 1 28 120VAC 8237A27H01 1 29 240VAC 8237A27H02 1 Shunt Trip Coils 30 24VDC 3759A76G14 1 31 48VDC 3759A76G11 1 32 125VDC 125VAC Cap Trip 3759A76G12 1 33 250VDC 240VAC Cap Trip 3759A76G13 1 Primary...

Страница 45: ...off Switch 699B199G04 1 44 Latch Check Switch 699B147H04 1 45 Position Switch 699B147H01 1 46 Position Switch 3759A93H02 1 47 Auxiliary Switch 5697B20H01 1 48 Trip D Shaft 694C638G01 1 49 Trip Latch H...

Страница 46: ...1 51 25kA 8796C85G02 1 52 31 5kA 8796C85G03 1 53 21 35kA 8796C85G04 1 54 Shock Absorber 5677B26H01 2 55 Front Panel w o ESCN 4D13655H02 1 56 Breaker Rail Wheel 5680B22G01 4 57 Shutter Drive Roller 568...

Страница 47: ...rness 61 Repair Kit 8796C82G01 1 Complete Replacement 62 STD 8796C82G02 1 63 With 2 AUX SW 8798C82G03 1 Undervoltage Kit 64 48VDC 8794C81G01 1 65 125VDC 8794C81G02 1 66 250VDC 8794C81G03 1 67 120VAC 8...

Страница 48: ...he contract between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PAR TICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF...

Отзывы: