I.L.15.01.T.K.

Page 13

Effective June 2000

remain on the emergency source until the
external contact is opened, when user is
certain that the threat of problems has
passed.  If the emergency source fails at
any time when in the Area Protection mode,
the switch will immediately transfer back to
the Normal source if it is Available.

The MP1-E controller allows the Test/Area
protection input to be disabled if the user
would like to prevent unauthorized users
from using the test switch or input contact.

Optional Feature 29 - Manual Return To
Normal – MP1-E Only

A manual operated momentary contact
(normally open) operates in conjunction with
the Manual Return to Normal option to
replace the TDEN timing function.  With the
manual mode set, closure of this contact will
prompt an immediate transfer bypassing the
TDEN time delay.  This ensures that a re-
transfer occurs only at the discretion of the
operator.

Optional Feature 32 - Time Delay Neutral

Provides a time delay in the transfer switch
neutral position when the load is transferred
in one or both directions.  This is to prevent
excessive inrush currents due to out-of-
phase switching of large inductive loads.  If
the TDN timer is programmed to 0 seconds,
the transfer switch shall operate as if the
TDN option is disabled.  Three optional
modes of Neutral Time Delay are available
as programmable:

(a)  TDN(NE) – Time Delay Neutral (from

Normal to Emergency)

(b)  TDN(EN) – Time Delay Neutral (from

Emergency to Normal)

(c)  TDN(G) – Time Delay Neutral (Both

directions)

8.2 External 

Options

There are also external options that may be
installed in a Cutler-Hammer Automatic
Transfer Switch.  A brief description is
provided.

Standard Feature 6D – 2 Position Test
Selector Switch (TSS)

Position 1 – “Auto”: The ATS will function
normally, transferring to the emergency
source when normal power is lost.

Position 2 – “Test”: The ATS will simulate
the loss of the normal source.  The switch
will transfer to source 2 after the Time Delay
Engine Start, and the TDNE has expired.
The ATS will return to the normal position
when the switch is return to “Auto”.

Option 6G

 is identical to the Test Selector

Switch except key operated.  Key removable
in “Auto” position.

Standard Feature 6H – 4 Position Test
Selector Switch (FPSS)

Position 1 – “Auto”: The ATS will function
normally, transferring to source 2 when
normal power is lost.

Position 2 – “Test”: The ATS will simulate
the loss of the normal source.  The switch
will transfer to source 2 after the Time Delay
Engine Start, and the TDNE has expired.
The ATS will return to the normal position
when the switch is returned to “Auto”.

Position 3 – “Engine Start”: The engine start
contacts will close, giving the genset a start
signal.  This position can be used to test the
correct connection of the engine start
terminals, or as a remote start.  The
controller with function normally and transfer
to the emergency if normal power is lost.

Position 4 – “Manual”: This will disconnect
the transfer motor, and prevent transfers in
either direction.  The ATS can be transferred
only by operating the manual transfer
handle.

Option 6J

 is identical to the Four Position

Selector Switch except key operated.  Key
removable in “Auto” position.

Optional Feature 12C – Normal
Connected Pilot light.

A green 30mm indication light indicates that
the load is connected to the normal source.

Optional Feature 12D –
Emergency Connected Pilot light.

A red 30mm indication light indicates that
the load is connected to the emergency
source.

Содержание Cutler-Hammer MP1 Series

Страница 1: ...I L 15 01 T K Effective June 2000 Instructions for Cutler Hammer MP1 Series Automatic Transfer Switches 30 1200A...

Страница 2: ......

Страница 3: ...AL AUTOMATIC TRANSFER SWITCH 5 4 3 TABLE 1 SYSTEMS COORDINATION INFORMATION 6 5 PERFORMANCE SPECIFICATIONS 7 6 DESCRIPTION OF OPERATION 8 6 1 INPUT PUSHBUTTONS 8 6 2 PROGRAM MODE 8 6 2 1 Password 8 6...

Страница 4: ......

Страница 5: ...in tort including negligence or strict liability extra contractually or otherwise shall not exceed the price of the Product or Service on which such liability is based 2 Receiving Handling and Storage...

Страница 6: ...position Two lifting lugs on the top of the enclosure are provided as standard on switches from 200 1200 Amps to facilitate installation 2 3 Storage Although well packaged this equipment is not suita...

Страница 7: ...utomatic transfer switch as self acting equipment for transferring one or more load conductor connections from one power source to another The same Standard also gives definitions for type A and type...

Страница 8: ...the reset procedure are located on the front of the operating mechanism 3 4 Definitions With respect to their use in this document and as they relate to automatic transfer switch operation the follow...

Страница 9: ...Horizontal Automatic Transfer Switch A complete line rated from 200 through 1200 Amperes at 600 Volts AC 50 or 60 Hertz The transfer mechanism consists of the transfer motor a gear train and two brea...

Страница 10: ...eaker kA Ratings when used with upsteam fuse kA ATS Ampere Rating 240V 480V 600V Max Fuse Rating Fuse Type 600V 30 100 65 25 200 J T 200 70 100 65 25 200 J T 200 100 100 65 25 200 J T 200 150 100 65 2...

Страница 11: ...age Dropout Range 105 to 120 of the nominal system voltage Overvoltage Pickup Range 103 to Dropout 2 of the nominal system voltage Underfrequency Dropout Range 90 to 97 of the nominal system frequency...

Страница 12: ...m mode each press of the Decrease key will decrease the displayed value by one The Decrease pushbutton will continue to scroll if it is pressed and not released Save Exit When in program mode and the...

Страница 13: ...rgency Source Connected This red LED displays the status of the transfer switch position It illuminates when the emergency source is available and the transfer switch is in emergency position Indicati...

Страница 14: ...fer switch operation Alarm Relay The full Form C contact of this relay may be wired to an alarm enunciator panel to indicate problem with the ATS This relay is normally energized to indicate an absenc...

Страница 15: ...elay Emergency to Normal Delays the transfer from the emergency source to the normal source to permit stabilization of the normal source before re transfer is made Timing begins when the normal source...

Страница 16: ...ame as the normal source and the alternate source will be considered the same as the emergency source All time delays e g TDNE TDEN will be a function of this feature and follow the preferred source T...

Страница 17: ...tch A brief description is provided Standard Feature 6D 2 Position Test Selector Switch TSS Position 1 Auto The ATS will function normally transferring to the emergency source when normal power is los...

Страница 18: ...n can in many cases eliminate the need for separate upstream overcurrent short circuit protection For safety purposes this option includes a lock out function that prevents further automatic transfer...

Страница 19: ...ut 2 to 99 Source 2 Undervoltage Pickup of nominal N OV DO 105 to 120 Source 1 Overvoltage Dropout of nominal N OV PU dropout 2 to 120 Source 1 Overvoltage Pickup of nominal E OV DO 105 to 120 Source...

Страница 20: ...xternal Contact 12C Normal Position Standard On faceplate 12D Emergency Position Standard On faceplate 12G Normal Source Available Standard On faceplate 12H Emergency Source Available Standard On face...

Страница 21: ...lts of problem solving steps taken and or readings taken of the system voltage that now appears on the load terminals A Gen Set Does Not Start When Test Switch is Operated and Held in Test Position 1...

Страница 22: ...cheduled basis Since equipment maintenance will consist mainly of keeping the equipment clean the frequency of maintenance will depend to a large extent on the cleanliness of the surroundings If a sig...

Страница 23: ...e control components time delay and voltage sensing relays for correct settings 7 If the horizontal mechanism is removed be sure that the scribe lines on the gears are in line When re assembling the d...

Страница 24: ...ler Hammer 403 East Lake Blvd Airdrie Alberta T4A 2G1 Canada tel 403 948 7955 fax 403 948 6967 www chfire com 2003 Eaton Corporation All Rights Reserved Printed in Canada Publication No I L 15 01 T K...

Отзывы: