5. Performance Specifications

The performance specifications for the ATS-MP1 Controller Board are given in Table 2:

Table 2 – Performance Specifications

Input Control Voltage

(50-150)%  of  

V

(IN,RMS)

                50/60 Hz

Voltage Measurements of:

Normal Source V

AB

Normal Source V

BC

Normal Source V

CA

Emergency Source V

AB

Emergency Source V

BC

Emergency Source V

CA

Voltage Measurement Range:

0 to 360 VAC RMS (50/60Hz) – 

MP1

0 to 750 VAC RMS (50/60Hz) – 

MP1-E

Voltage Measurement Accuracy:

±

 2% of reading over the monitoring range

Frequency Measurements of:

Normal Source (S1), Emergency Source (S2)

Frequency Measurement Range:

40 Hz to 70 Hz

Frequency Measurement Accuracy

±

 0.3 Hz over the measurement range

Undervoltage Dropout Range:

50% to 97% of the nominal system voltage

Undervoltage Pickup Range:

(D2%) to 99% of the nominal system voltage

Overvoltage Dropout Range:

105% to 120% of the nominal system voltage

Overvoltage Pickup Range:

103% to (Dropout –2%) of the nominal system voltage

Underfrequency Dropout Range:

90% to 97% of the nominal system frequency

Underfrequency Pickup Range:

(D 1Hz) to 99% of the nominal system frequency

Overfrequency Dropout Range:

103% to 110% of the nominal system frequency

Overfrequency Pickup Range:

101% to (Dropout – 1Hz) of the nominal system frequency

Operating Temperature Range

-20

°

C to + 70

°

C

Storage Temperature Range

-35

°

C to + 85

°

C

Operating Humidity

0 to 95% relative humidity (non-condensing)

Generator Start Relay

5A, 1/6 HP @ 250VAC
5A @ 30VDC with a 30W maximum load

Alarm Relay

10A, 1-3 HP @ 250VAC
10A @ 30VDC

Table 3 - Applicable Test Standards

UL 991
Canadian Standards Association Conformance (CSA)
UL 1008 / CSA 22.2 No 178.22
Dielectric test
FCC Part 15
Conducted/Radiated Emissions (Class A)
CISPR 11
Conducted/Radiated Emissions (Class A)
IEC 1000-2
Electrostatic Discharge test
IEC 1000-3
Radiated Susceptibility tests
IEC 1000-4
Fast Transient tests
IEC 1000-5
Surge Withstand tests

Содержание Cutler-Hammer MP1 Series

Страница 1: ...I L 15 01 T K Effective June 2000 Instructions for Cutler Hammer MP1 Series Automatic Transfer Switches 30 1200A...

Страница 2: ......

Страница 3: ...AL AUTOMATIC TRANSFER SWITCH 5 4 3 TABLE 1 SYSTEMS COORDINATION INFORMATION 6 5 PERFORMANCE SPECIFICATIONS 7 6 DESCRIPTION OF OPERATION 8 6 1 INPUT PUSHBUTTONS 8 6 2 PROGRAM MODE 8 6 2 1 Password 8 6...

Страница 4: ......

Страница 5: ...in tort including negligence or strict liability extra contractually or otherwise shall not exceed the price of the Product or Service on which such liability is based 2 Receiving Handling and Storage...

Страница 6: ...position Two lifting lugs on the top of the enclosure are provided as standard on switches from 200 1200 Amps to facilitate installation 2 3 Storage Although well packaged this equipment is not suita...

Страница 7: ...utomatic transfer switch as self acting equipment for transferring one or more load conductor connections from one power source to another The same Standard also gives definitions for type A and type...

Страница 8: ...the reset procedure are located on the front of the operating mechanism 3 4 Definitions With respect to their use in this document and as they relate to automatic transfer switch operation the follow...

Страница 9: ...Horizontal Automatic Transfer Switch A complete line rated from 200 through 1200 Amperes at 600 Volts AC 50 or 60 Hertz The transfer mechanism consists of the transfer motor a gear train and two brea...

Страница 10: ...eaker kA Ratings when used with upsteam fuse kA ATS Ampere Rating 240V 480V 600V Max Fuse Rating Fuse Type 600V 30 100 65 25 200 J T 200 70 100 65 25 200 J T 200 100 100 65 25 200 J T 200 150 100 65 2...

Страница 11: ...age Dropout Range 105 to 120 of the nominal system voltage Overvoltage Pickup Range 103 to Dropout 2 of the nominal system voltage Underfrequency Dropout Range 90 to 97 of the nominal system frequency...

Страница 12: ...m mode each press of the Decrease key will decrease the displayed value by one The Decrease pushbutton will continue to scroll if it is pressed and not released Save Exit When in program mode and the...

Страница 13: ...rgency Source Connected This red LED displays the status of the transfer switch position It illuminates when the emergency source is available and the transfer switch is in emergency position Indicati...

Страница 14: ...fer switch operation Alarm Relay The full Form C contact of this relay may be wired to an alarm enunciator panel to indicate problem with the ATS This relay is normally energized to indicate an absenc...

Страница 15: ...elay Emergency to Normal Delays the transfer from the emergency source to the normal source to permit stabilization of the normal source before re transfer is made Timing begins when the normal source...

Страница 16: ...ame as the normal source and the alternate source will be considered the same as the emergency source All time delays e g TDNE TDEN will be a function of this feature and follow the preferred source T...

Страница 17: ...tch A brief description is provided Standard Feature 6D 2 Position Test Selector Switch TSS Position 1 Auto The ATS will function normally transferring to the emergency source when normal power is los...

Страница 18: ...n can in many cases eliminate the need for separate upstream overcurrent short circuit protection For safety purposes this option includes a lock out function that prevents further automatic transfer...

Страница 19: ...ut 2 to 99 Source 2 Undervoltage Pickup of nominal N OV DO 105 to 120 Source 1 Overvoltage Dropout of nominal N OV PU dropout 2 to 120 Source 1 Overvoltage Pickup of nominal E OV DO 105 to 120 Source...

Страница 20: ...xternal Contact 12C Normal Position Standard On faceplate 12D Emergency Position Standard On faceplate 12G Normal Source Available Standard On faceplate 12H Emergency Source Available Standard On face...

Страница 21: ...lts of problem solving steps taken and or readings taken of the system voltage that now appears on the load terminals A Gen Set Does Not Start When Test Switch is Operated and Held in Test Position 1...

Страница 22: ...cheduled basis Since equipment maintenance will consist mainly of keeping the equipment clean the frequency of maintenance will depend to a large extent on the cleanliness of the surroundings If a sig...

Страница 23: ...e control components time delay and voltage sensing relays for correct settings 7 If the horizontal mechanism is removed be sure that the scribe lines on the gears are in line When re assembling the d...

Страница 24: ...ler Hammer 403 East Lake Blvd Airdrie Alberta T4A 2G1 Canada tel 403 948 7955 fax 403 948 6967 www chfire com 2003 Eaton Corporation All Rights Reserved Printed in Canada Publication No I L 15 01 T K...

Отзывы: