IQ DP-4000
SECTION 5 - PROGRAMMING THE IQ DP-4000
TD 17548B
36
= OFF
= ON
Ranges
Switch Settings
(Set all 8 S2 switches)
Load Shed,
% of nominal
Rotary
Switch
S3.E
S3.D
Setpoint
Switch
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
Restore Load,
% of nominal
Rotary
Switch
S3.E
S3.D
Setpoint
Switch
S2.5
S2.6
S2.7
S2.8
S2.7
S2.8
10
off
off
off
off
off
off
12
on
off
off
off
off
off
14
off
on
off
off
off
off
16
on
on
off
off
off
off
18
off
off
on
off
off
off
20
on
off
on
off
off
off
22
off
on
on
off
off
off
24
on
on
on
off
off
off
26
off
off
off
on
off
off
28
on
off
off
on
off
off
30
off
on
off
on
off
off
32
on
on
off
on
off
off
34
off
off
on
on
off
off
36
on
off
on
on
off
off
38
off
on
on
on
off
off
40
on
on
on
on
off
off
42
off
off
off
off
on
off
44
on
off
off
off
on
off
46
off
on
off
off
on
off
48
on
on
off
off
on
off
50
off
off
on
off
on
off
52
on
off
on
off
on
off
54
off
on
on
off
on
off
56
on
on
on
off
on
off
58
off
off
off
on
on
off
60
on
off
off
on
on
off
62
off
on
off
on
on
off
64
on
on
off
on
on
off
66
off
off
on
on
on
off
68
on
off
on
on
on
off
70
off
on
on
on
on
off
72
on
on
on
on
on
off
74
off
off
off
off
off
on
76
on
off
off
off
off
on
78
off
on
off
off
off
on
80
on
on
off
off
off
on
82
off
off
on
off
off
on
Table 5.Y Load Shed and Restore Load Settings (continued on next page)