The  Digitrip  RMS 51 0 Trip Unit is completely 

self-con­

tained and when the circuit breaker is closed, 

requires 

no 

external control power to operate its 

protection 

sys­

tems. 

It operates from current signal levels 

and  control 

power derived  through current sensors 

integrally 

mounted in the circuit breaker. 

The Digitrip RMS 510 Trip Unit is available in six 

different 

types. Each trip unit may be equipped with 

a  maximum 

of 

five phase and  two ground (time-current) adjustments to 
meet specific application requirements. The 

types  of pro­

tection available for 

each 

model include the 

following, 

which are illustrated in Figures 2.1  through 2.6: 

Protection 

Types 

Refer to 
Figure 

Long  Time/Instantaneous 

Ll* 

2.1 

Long Time/Short Time 

LS* 

2.2 

Long Time/Short Time/Instantaneous 

LSI* 

2.3 

Long  Time/Instantaneous/Ground 

LIG 

2.4 

Long Time/Short Time/Ground 

LSG 

2.5 

Long Time/Short Time/Instantaneous/ 

LSIG 

2.6 

Ground 

I.L. 29-8858 

Note*:  RMS Digitrip Type  Ll,  LS, and LSI trip  units 

can be applied on 3-pole or 4-pole circuit breakers for 

protection of the neutral circuit, 

IF 

the circuit breaker 

is  wired and MARKED for NEUTRAL PROTECTION. 

Refer to the N ational Electric Code for appropriate 

application of 4-pole breakers. 

1.2 Information 

Light Emitting Diodes (LED's) on the face of the trip unit 

light "Red"  to indicate the 

reason for an automatic trip 

operation.  The  battery 

in the rating plug maintains the 

reason for trip indication following an automatic trip oper­

ation,  until the "TRIP RESET" button is pushed. 

T he 

"Green" LED in the lower right  corner "blinks" to indi­

cate the trip unit is  operating 

normally. The battery in the 

rating 

plug is "OK" if 

the 

LED lights "Green" when the 

"battery check" button next to it is pushed. (See 
Section  6.). 

Note:  The  Digitrip  RMS 

510 

provides all of its  protec­

tion functions regardless of the status of the battery. 

The  battery serves only to maintain the  indication of 

the  reason for automatic trip. 

Fig. 

LED's 

light 

"'RED" 

to indicate 

cause of trip 

Tome-Current Curve 

for Ground 
Protection 

Trip 

Unit 

Operational 
Status 
"Blinking 
Green"=OK 

Adjust  Protection  Settings  for 

Desired 

Values with  Rotary  Swttches 

Digitrip RMS 

510 

Trip Unit Model LSIG  with Rating Plug 

Effective May  1997 

www 

. ElectricalPartManuals 

. com 

Содержание Cutler-Hammer Digitrip RMS 510 Trip Unit

Страница 1: ...ILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES CUTLER HAMMER IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTAL LATION OF ITS PRODUCTS It is strongly urged that the user observe all recommen dations warnings and cautio...

Страница 2: ...protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PROTECTION Refer to the National Electric Code for appropriate application of 4 pole breakers 1 2 Information Light Emitting Diodes LED s on the face of the trip unit light Red to indicate the reason for an automatic trip operation The battery in the rating plug maintains the reason for trip indication followi...

Страница 3: ...Protection LI Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection LIG w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 4: ...me Instantaneous Ground Protection LSIG The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 Individual product instruction leaflets referenced in Section 9 0 illus trate typical Digitrip RMS Trip Units installed in specific breakers T he trip unit employs the Cutler Hammer Inc custom designed...

Страница 5: ...0 of the frame current sensor rating the green LED will flash On and Off onceeach second to indicate the trip unit is energized and operating properly Note If the LED is steadily GREEN i e not flash ing the trip unit is not ready Effective May 1997 3 3 Test Provisions See Section 5 0 3 4 DIScriminator Making Current Release For Types LS and LSG trip units only When the Digitrip RMS 510 Trip Unit i...

Страница 6: ...ream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 8858 Note If a breaker M receives a Zone Interlocking signal from another breaker F but the fault current level is less than the trip unit setting for breaker M the signal from the other breaker F will no...

Страница 7: ... earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 10 minutes it has reset fully so that next Long Delay trip time will again be the Set ting value In certain applications it may be desirable to dis able the LTM function The LTM function can be disabled by first opening the breaker and then removing the Rating Plug See Figures ...

Страница 8: ...licable to currents less than eight 8 times 1 the Long Delay Setting For currents greater than 8 times 1 the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Setting There are eight 8 available Instantaneous Current Set tings as illustrated in Fig 4 5 Six settings are in the range from 2 to 6 times In the rating plug value and th...

Страница 9: ...0 240 300 400 a w 600 150 180 210 240 300 360 450 600 Q_ 630 158 189 221 252 315 378 473 630 s 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 J 400 500 600 750 1000 _J 1200 300 360 420 480 600 720 900 1200 Q_ 9 1250 312 375 438 500 625 750 936 1200 z 1600 400 480 560 640 800 960 1200 1200 a 2000 500 600 700 800 1000 1200 1200 1200 0 2400 600 720 840 960 1200 1200 1200 1200 w _J _J 2500 625...

Страница 10: ...utomatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip Unit A CAUTION TESTING A CIRCUIT BREAKER UNDER TRIP CON DITIONS WHILE IT IS IN SERVICE AND CARRYING LOAD CURRENT WHETHER DONE BY INTERNAL OR EXTERNAL MEANS IS NOT RECOMMENDED ANY TRIPPING OPERATION WILL CAUSE DISRUP TION OF SE...

Страница 11: ...s than10 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indicating that there is enough current flowing to pro vide the power necessary to operate the trip unit In the event the Unit Status LED is either lighted GREEN or OFF continuously there is NOT enough cur rent flowing to power ...

Страница 12: ...ng make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting lr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current exceeds 50 of lr 2 Place the Test Amps selector switch See Fig 5 in one of the two Trip test settings i e 6T or GFT 3 Depress the black Test pushbutton See Fig 5 and release it the test is initiated when ...

Страница 13: ...r Rat1ng Plug Identification Fig 6 Battery Check Pushbutton 1 Typical Rating Plug Values for Sho t Delay S1 and S2 Instantaneous M1 and M2 Set11llQS Battery OK if LED lights GREEN when Battery Check Button is Pushed Page 13 obtained from the following companies under their type designation indicated Company Model Varta Batteries Inc 150 Clarbrook Road Elmsford N Y 10523 Duracell South Broadway Tar...

Страница 14: ...cuit breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity to complete the trip unit See Fig 1 Rating plugs have two current ratings listed on their covers See Fig 6 1 the Must be used with Frame Rated cur I L 29 8858 rent value or Sensor Rated if applica b...

Страница 15: ...me Circuit Breaker APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used The branch breaker will trip clearing the fault in 0 1 s Fault 2 The feeder breaker will trip clearing the fault in 0 3 s Fault 1 The breaker will trip clearing the fault in 0 5 s CASE 2 There is Zo...

Страница 16: ...he maximum distance between first and last zone is 250 feet 110 m A3 A Maximum of 20 breakers may be con nected in parallel in one Zone Legend Common Ungrounded Short Delay Output Signal to Higher Level Zone Short Delay Input Signal from Lower Level Zone Ground Output Signal to Higher Level Zone Ground Input Signal from Lower Level Zone ault at Location 2 2 M2 0 5 Sec F21 F22 F23 0 1 Sec 0 1 Sec 0...

Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...I L 29 8858 Page 19 0 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 20: ...OSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer Inc be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any special indirect incidental or consequential damage or loss whatsoever incl...

Отзывы: