INM MTL 130-0186 Rev 8
15
Send
Function
Reply (verbose)
Reply (terse)
Limits (where applicable)
Notes
AxCy
Calibration
C9 Load def=0
C9=0
0 or 1
Load defaults
C8 Sens 2 os=0.00
C8 =0.00
Cell offset
C7 Sens 2 K=1
C7 =45.0
Cell slope
C6 Sens 2 H cal =100%
C6 =0
N/A
C5 Sens 2 L cal=0%
C5 =100
N/A
C4 Sens 1 os=0.00
C4 =0.00
Cell offset.
C3 Sens 1 K=45.0
C3 =45.0
Cell slope.
C2 Sens 1 H cal =100%
C2 =0
Zr limits
Calibrate high.
C1 Sens 1 L cal=0%
C1 =100
Zr limits
Calibrate low.
Note:- Sending AxC1=xxx calibrates to xxx, and AxC1 RETURNS the last C1 cal value, but changes nothing.
AxC9=1 makes the instrument load HARD CODED DEFAULTS. User will be asked to type ‘y’ to confirm, or load will be abandoned.
AxDy
Data (read only)
D6 ADC 3 = 12345cts
D6 = 12345
ADC raw counts
D5 ADC 2 = 12345cts
D5 = 12345
ADC raw counts
D4 ADC 1 = 12345cts
D4 = 12345
ADC raw counts
D3 Sens 3 = N/A
D3 =0
N/A
D2 Sens 2 = 11.56mV
D2 =11.56
Thermocouple mV
D1 Sens 1 = 11.55mV
D1 =11.55
Oxygen cell mV
AxEy
Error logs
(read only except E9)
E9 Clear Log=0
E9=0
1 to clear logs
Clear all counters
E8 Calibration=0
E8=0
Calibration error counter
E7 Sensor=0
E7=0
Sensors error counter
E6 AO=0
E6=0
Analogue output counter
E5 Float=0
E5 =0
Float error counter
E4 CRC=0
E4 =0
EEPROM CRC error counter
E3 Other=0
E3 =0
Other error counter
E2 Last=0
E2 =0
Last error code
E1 Current=0
E1 =0
Current error code
AxIy
Input (Read only)
I17 R3 SP=N\A
I17 =N\A
I16 R2 BG=N/A
I16 =N/A
I15 R2 SP=N/A
I15 =N/A
I14 R2 MMW comp=1
I14 =1
I13 R2 RangeT =100
I13 =100
I12 R2 RangeB =0
I12 =0
I11 R2 Os Range=0
I11 =0
I10 R2 K Range=1
I10=0
I9 R2 Base K =-4.7
I9=1
I8 R1 BG=N2
I8 =N2
I7 R1 SP=O2
I7 =O2
I6 R1 MMW comp=1.00
I6 =1.000
I5 R1 RangeT =100
I5 = 100
I4 R1 RangeB =0
I4 = 0
I3 R1 Os Range=0.01
I3 =0.01
I2 R1 K Range=1
I2 =1
I1 R1 Base K =-4.7
I1 =-4.7
continued on the next page
Send
Function
Reply (verbose)
Reply (terse)
Limits (where applicable)
Notes
Table 1
- Common groups