INM F890 Rev 1

5 .8  Diagnostic Segment Connectors

Two Diagnostic Segment connectors are available for use in conjunction with the 
optional F809F Diagnostic Module.   These connectors are only available on units with 
date codes after 0726.  Please see the Installation Manual for the F809F for further 
information.  Note that the Diagnostic Segment is completely isolated from any of 
the 8 segments powered by the F890-CA carrier.  This includes the screen for the 
Diagnostic Segment.

Pin No . 

Connection

Pin No . 

Connection

94

Diag Seg +

97

Diag Seg +

95

Diag Seg S

98

Diag Seg S

96

Diag  Seg -

99

Diag  Seg -

TESTING

6 .1  F801 Status and Alarm LEDs

The F801 or F802 Power Modules are fitted with nine LEDs, eight to indicate segment 
status and one to signify an Alarm condition.

Fault Condition

Segment LED

Fault

Alarm contact status

No Fault

Green

Off

Closed

Segment shorted

Off

Red

Open

Output <20V

Off

Red

Open

Input   <16V

Off (All)

Red

Open

ROUTINE MAINTENANCE

Check the general condition of the installation occasionally to make sure that no 
deterioration has occurred. At least every two years (and more frequently for particularly 
harsh environments) check:

•  the condition of wire connections, terminations, and screens.
•  the dc output voltage on each of the eight fieldbus segments is >21.5V for the F801 

or >28V for the F802. This can be performed using a multi-meter or a Relcom FBT-6 
Fieldbus Monitor.

•  the segment LEDs on the Power Module(s) are functioning and the Alarm LED is 

not lit .

•  the Power Module retaining screws are tight.
•  there are no signs of damage or corrosion.

Содержание Crouse-Hinds MTL F890

Страница 1: ...MTL F890 8 Segment Redundant Fieldbus Power Supply for use with non proprietary cabled systems March 2022 INM F890 Rev 1 Instruction manual MTL fieldbus networks...

Страница 2: ...ii INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 3: ...5 5 ELECTRICAL CONNECTIONS 5 5 1 DC Power Requirements 6 5 2 Power A and Power B 7 5 2 1 Redundancy 7 5 2 2 Terminator 7 5 3 Alarm Connection 7 5 4 FInal Segment Connections 8 5 5 Field Segment Conne...

Страница 4: ...dule may be used where redundancy is not required 2 DESCRIPTION For maximum reliability the module carrier contains no components and only provides interconnections between the Power Modules and the e...

Страница 5: ...xtinguished and the red Alarm LED is lit Redundant 24V DC nom input power is connected to the F890 CA carrier using two part pluggable connectors Field wiring connections are available with either plu...

Страница 6: ...s www mtl fieldbus com Relcom Inspect Clamps Inspect Clamps Shield Ground Option Ground SG 51 52 53 Rev E 0 S S S S S S S S 20 21 22 17 18 19 14 15 16 11 12 13 23 24 25 26 27 28 29 30 31 32 33 34 Segm...

Страница 7: ...ure that the permitted ambient temperature range of 40 C to 65 C derate to 50 C for the F802 when loaded above 60 of its full load rating is not exceeded Allow for power dissipation within the enclosu...

Страница 8: ...carrier with four screw mountings There are four locating connectors two for each module on the module carrier along with mating connectors in the F801 or F802 module Align the module with the retaini...

Страница 9: ...vided allowing the use of bulk power supplies with a supply range of 19 2 30VDC Input power cabling and over current protection devices must be chosen to match the current consumption An F890 system o...

Страница 10: ...ion Power must be connected to Power B terminals if live replacement of Power Module A is necessary since Power B terminals feed the Power Module B connector 5 2 2 Terminator A single terminator is pr...

Страница 11: ...28 Segment 6 17 Segment 3 29 Segment 7 18 Segment 3 S 30 Segment 7 S 19 Segment 3 31 Segment 7 20 Segment 4 32 Segment 8 21 Segment 4 S 33 Segment 8 S 22 Segment 4 34 Segment 8 The host cable length s...

Страница 12: ...the connector for the indicated function When using the screen grounding facility on the F890 carrier the jumper must be installed correctly Figure 7a and an Instrumentation Ground must be routed to...

Страница 13: ...ith nine LEDs eight to indicate segment status and one to signify an Alarm condition Fault Condition Segment LED Fault Alarm contact status No Fault Green Off Closed Segment shorted Off Red Open Outpu...

Страница 14: ...11 INM F890 Rev 1 8 FM CONTROL DRAWINGS...

Страница 15: ...ed in place of the missing F801 or F802 module 24VDC Power Supplies may be installed in the Non hazardous area Vmax 24VDC F801 30VDC F802 24VDC Power Supply A 24VDC Power Supply A This is a Chassis Gr...

Страница 16: ...clause 4 2 of EN 60079 17 b This equipment has been designed to provide protection against all the relevant additional hazards referred to in Annex II of the directive such as those in clause 1 2 7 c...

Страница 17: ...ified product 9 5 Marking Each device is marked in compliance with the Directive Regulation This information applies to products manufactured during or after the year 2007 Typical certification markin...

Страница 18: ...15 INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 19: ...Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Milano...

Отзывы: