Eaton Crouse-Hinds MTL F890 Скачать руководство пользователя страница 12

9

INM F890 Rev 1

78

Segment 3  -

66

Segment 7  -

73

Segment 4 +

61

Segment 8 +

74

Segment 4 S

62

Segment 8 S

75

Segment 4  -

63

Segment 8  -

5 .6  Cable Screen / Ground Connections

For revision E .0 or higher units

 – Provisions have been made to facilitate tying the 

8 screens together and bringing them to the common Screen Ground terminal 53.  
This is a user selectable option that is determined based on the position of the jumper 
installed in the “Shield Ground Option” connector.  Figures 7a and 7b illustrate the two 
possible positions for the jumper.  The carrier is delivered with the jumper installed as 
shown in figure 7b.  As indicated in the text on the jumper, the screens are isolated.  
To tie the 8 screens together and route them to the SG terminal, remove, reverse and 
reinstall the jumper as shown in figure 7a.  The arrow next to the text indicates which 
direction to install the jumper into the connector for the indicated function.

When using the screen grounding facility on the F890 carrier, the jumper must be 
installed correctly (Figure 7a) and an Instrumentation Ground must be routed to 
Terminal 53 .  Fieldbus segments require proper grounding in order to function properly,

 

 Figure 7a  

 

 

                 Figure 7b

For earlier units, 

the segment screens are not linked together nor tied to a common 

ground connection, so screen grounding must be done externally from the carrier.  The 
carrier revision is on the board surface between the two F80x modules (see figure 
2).  No revision number existed before revision E.0.  If the screens of the fieldbus 
cables are required to be earthed in the equipment cabinet housing the F890 system, 
a separate earth bar, connected to local instrumentation earth, should be used.

5 .7  Chassis Ground Connection

The chassis of the carrier should be connected to a Safety or Instrumentation Ground 
using either of the two screw terminals 51 or 52.  This ground is needed for the F890 
system to meet Electromagnetic Compatibility and Electrical Safety requirements.

Содержание Crouse-Hinds MTL F890

Страница 1: ...MTL F890 8 Segment Redundant Fieldbus Power Supply for use with non proprietary cabled systems March 2022 INM F890 Rev 1 Instruction manual MTL fieldbus networks...

Страница 2: ...ii INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 3: ...5 5 ELECTRICAL CONNECTIONS 5 5 1 DC Power Requirements 6 5 2 Power A and Power B 7 5 2 1 Redundancy 7 5 2 2 Terminator 7 5 3 Alarm Connection 7 5 4 FInal Segment Connections 8 5 5 Field Segment Conne...

Страница 4: ...dule may be used where redundancy is not required 2 DESCRIPTION For maximum reliability the module carrier contains no components and only provides interconnections between the Power Modules and the e...

Страница 5: ...xtinguished and the red Alarm LED is lit Redundant 24V DC nom input power is connected to the F890 CA carrier using two part pluggable connectors Field wiring connections are available with either plu...

Страница 6: ...s www mtl fieldbus com Relcom Inspect Clamps Inspect Clamps Shield Ground Option Ground SG 51 52 53 Rev E 0 S S S S S S S S 20 21 22 17 18 19 14 15 16 11 12 13 23 24 25 26 27 28 29 30 31 32 33 34 Segm...

Страница 7: ...ure that the permitted ambient temperature range of 40 C to 65 C derate to 50 C for the F802 when loaded above 60 of its full load rating is not exceeded Allow for power dissipation within the enclosu...

Страница 8: ...carrier with four screw mountings There are four locating connectors two for each module on the module carrier along with mating connectors in the F801 or F802 module Align the module with the retaini...

Страница 9: ...vided allowing the use of bulk power supplies with a supply range of 19 2 30VDC Input power cabling and over current protection devices must be chosen to match the current consumption An F890 system o...

Страница 10: ...ion Power must be connected to Power B terminals if live replacement of Power Module A is necessary since Power B terminals feed the Power Module B connector 5 2 2 Terminator A single terminator is pr...

Страница 11: ...28 Segment 6 17 Segment 3 29 Segment 7 18 Segment 3 S 30 Segment 7 S 19 Segment 3 31 Segment 7 20 Segment 4 32 Segment 8 21 Segment 4 S 33 Segment 8 S 22 Segment 4 34 Segment 8 The host cable length s...

Страница 12: ...the connector for the indicated function When using the screen grounding facility on the F890 carrier the jumper must be installed correctly Figure 7a and an Instrumentation Ground must be routed to...

Страница 13: ...ith nine LEDs eight to indicate segment status and one to signify an Alarm condition Fault Condition Segment LED Fault Alarm contact status No Fault Green Off Closed Segment shorted Off Red Open Outpu...

Страница 14: ...11 INM F890 Rev 1 8 FM CONTROL DRAWINGS...

Страница 15: ...ed in place of the missing F801 or F802 module 24VDC Power Supplies may be installed in the Non hazardous area Vmax 24VDC F801 30VDC F802 24VDC Power Supply A 24VDC Power Supply A This is a Chassis Gr...

Страница 16: ...clause 4 2 of EN 60079 17 b This equipment has been designed to provide protection against all the relevant additional hazards referred to in Annex II of the directive such as those in clause 1 2 7 c...

Страница 17: ...ified product 9 5 Marking Each device is marked in compliance with the Directive Regulation This information applies to products manufactured during or after the year 2007 Typical certification markin...

Страница 18: ...15 INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 19: ...Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Milano...

Отзывы: