Explosion protected LED-exit luminaire
Series: EXIT, EXIT 24 V and EXIT V-CG-S
Address
switch 1
Address
switch 2
Luminaire
address
0
0
Monitoring off
0
1
1
0
2
2
...
...
...
1
0
10
1
1
11
...
...
...
...
...
...
2
0
20
2
1
not permissable
...
...
...
9
9
not permissable
4. Installation EXIT
The respective national regulations as
well as the general rules of engineering
which apply to the installation and operati-
on of explosion protected apparatus will
have to be observed (IEC/EN 60079-14)!
Transport and storage of the luminaire is
permitted in original packing and specified
position only!
3. Conformity with standards
The light fitting is suitable for use in zone 1, 2
and 21, 22 hazardous areas acc. to
IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
They have been designed, manufactured
and tested according to the state of the art
and to DIN EN ISO 9001:2008 and
EN ISO/IEC 80079-34:2011.
The light fitting is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
2. Technical data
ATEX type examination certificate:
BVS 09 ATEX E 029
Marking acc. to 94/9/EG and standard:
EN 60079-0:
ta
max
+ 40 °C:
D
II 2 G Ex e ib mb IIC T6 Gb
ta
max
+ 50 °C:
D
II 2 G Ex e ib mb IIC T5 Gb
Exit V-CG-S
ta
max
+ 50 °C:
D
II 2 G Ex e ib mb IIC T4 Gb
D
II 2 D Ex tb IIIC T80°C Db
IECEx type examination certificate:
IECEx BVS 13.0017
Category of application:
IEC 60079-0:
ta
max
+ 40 °C:
Ex e ib mb IIC T6 Gb
ta
max
+ 50 °C:
Ex e ib mb IIC T5 Gb
Exit V-CG-S
ta
max
+ 50 °C:
Ex e ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Rated voltage AC:
EXIT 24 V
non-permissible
EXIT
110 V - 277 V*
EXIT V-CG-S
220 V - 254 V*
Rated voltage DC:
EXIT 24 V
12 - 24 V DC -15%/+ 20%
EXIT
110 V - 250 V *
EXIT V-CG-S
195 V - 250 V *
Rated frequency
50 - 60 Hz
Rated current
110 V AC/DC:
0.05 A
230 V AC/DC:
0.025 A
Insulation class to IEC/EN 61140:
I
Degree of protection accd. IEC/EN 60529
IP 66
Operation temperature:
(Deviating temperatures possible with special versions)
-20 °C to +40°C/+50°C
Storage temperature in original packing:
-20°C to +50°C
Weight EXIT / EXIT 24 V:
approx. 2,0 kg
Weight EXIT V-CG-S:
approx. 2,2 kg
Supply terminal clamping capacity 2 x per
terminal:
3 x 2.5 mm²
Ex-e cable entry
Standard version
M20 x 1,5 for cable Ø 7 to 13 mm
suitable cables and test torques of the
pressure srew
Ø
Nm
seel 1+2
1
2
min.
max.
(1)(2)
7.0
9.0
1.5
1.4
seel 2
1
2
min.
max.
(2)
9.5
13.0
1.0
1.7
metal:
M20x1.5 thread
Test torque for M 20 x 1.5 Ex-e cable entry:
2.7 Nm
Test torque for mounting screws cover:
2.4 Nm
*
max. permissable tolerances accd. IEC/EN 60079-0
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future
maintenance work on the cable entry.
1. Legende
Warning
This symbol warns of a serious hazard.
Failure to observe this warning may result
in death or the destruction of property.
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result
in the total failure of the device or the
system or plant to which it is connected.
1.1 Safety instructions
For skilled electricians and
instructed personnel in accordance with
national legislation, including the
relevant standards and, where
applicable, in acc. with
IEC/EN 60079-14 on electrical
apparatus for explosive atmospheres.
– The light fitting must not be operated in
zone 0 or 20 hazardous areas!
– The technical data indicated on the light
fitting are to be observed!
– The requirements of the
EN/IEC 60079-31 regarding excessive
dust deposits and temperature to be
considered from the user.
– Changes of the design and modificati-
ons to the light fitting are not permit-
ted!
– The light fitting shall be operated as
intended and only in undamaged and
perfect condition!
– Only genuine CEAG/Cooper
Crouse-Hinds GmbH (CCH) spare parts
may be used for replacement!
– Repairs that affect the explosion
protection (see national standard), may
only be carried out by CEAG/CCH or a
qualified “electrician”!
– Do not keep these operating instruc-
tions inside the light fitting during
operation!
The national safety rules and regulations
for pre vention of accidents and the
following safety in structions which are
marked with an ( ) in these operating
instruction, will have to be observed!
Fig. 4 Addressing