background image

APPLICATION

FMV 1000 Series Floodlights are suitable for use in the following hazardous 
(classified) locations as defined by the National Electrical Code (NEC

®

):

•  Class I, Division 2, Groups A, B, C D
•  Class I, Zone 2, AEx nR (AEx nA nR with outlet box), Group IIC
•  Wet Locations
•  IP56

This luminaire is a restricted breathing product.  Restricted breathing, identified 
by the marking nR, means that an enclosure is sufficiently well sealed to limit the 
entry of flammable gas.

The Champ

®

 FMV 1000 Series comes standard as a “restricted breathing” 

luminaire.  That means it restricts vapors and gases from entering inside the 
luminaire.  Therefore, please retain and use the sealing cord connector (located 
on the bottom near trunnion mount of the luminaire) with 16-3 type SOW or equal 

cord.

Refer to the floodlight nameplate for specific classification information, maximum 
ambient temperature suitability, and corresponding operating temperature 
(T-Number).

Champ

®

 FMV 1000 Series Floodlight is designed for use indoors and outdoors 

in industrial locations where moisture, dirt, corrosion, vibration, and rough usage 
may be present.  Typical applications include process areas, storage areas, loading 
docks, rail yards, building perimeters, parking areas, sports applications, etc.

Champ

®

 FMV 1000 Series Floodlights are trunnion mounted and provided with a 

choice of voltages for the following light sources and wattages: 
•  1000W High Pressure Sodium (HPS)
•  1000W Metal Halide (MH)

IF 1515  •  10/14 

Copyright © 2014, Eaton’s Crouse-Hinds Business 

Page 1

Champ

®

 High Wattage Floodlight - 1000 Watts

Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1515

WARNING

To avoid electric shock:

•  Be certain power is OFF before and during installation and maintenance.
•  Fixture must be supplied by a wiring system with an equipment grounding 

conductor.

To avoid decreased lamp and fixture life, as well as risk of ignition:

•  Use only lamp type and wattage specified on nameplate of fixture.
•  Keep tightly closed when in operation.
•  Do not position the fixture beyond the aiming range limits.

 

To avoid burning hands: 

While performing maintenance, make sure lens and lamp are cool.

 

WARNING

To avoid the risk of fire and electric shock, this product should be installed by 
a qualified electrician only.

Read and follow these instructions carefully for installation and maintenance to 

achieve optimum performance.

WARNING

To avoid explosion: 

Make sure the supply voltage is the same as the floodlight voltage.

Do not install where the marked operating temperatures exceed the ignition 
temperature of the hazardous atmosphere.

Do not operate in ambient temperatures above those indicated on the floodlight 
nameplate.

Do not position the floodlight beyond the aiming range limits depicted on page 
2.  

Use only the lamp and wattage specified on the floodlight nameplate.

Use proper supply wiring as specified on the floodlight nameplate.

All gasket seals must be clean.

Before opening, electrical power to the floodlight must be turned off.  Keep 
tightly closed when in operation.

To maintain restricted breathing properties, do not substitute cable fitting 
supplied with fixture.

Figure 1

Отзывы: