Installation procedure

All parts should be inspected for damage before using. If 

there is evidence of physical damage, the unit should not be 

installed unless approved by your Eaton representative.

Bolt-in assembly

ote:

N

The tank wall should have a 1.325 (34 mm) diameter 

hole with an anti-rotation key, (refer to Figure 8). 

Switch should be located to ensure recommended 

clearances in Figure 6 are maintained.

1.  Switch should be mounted to four (4) couplings on the 

inside of the tank wall (refer to Figure 6 for coupling 

pattern) using 3/8" x .75" (10M x 19 mm, if metric 

couplings are being used) long bolts with lock washers, 

(not supplied).

2.  Install the gasket over the switch shaft sealing gland 

and insert the switch assembly through the tank hole. 

Position the switch with the open sides of the switch 

block facing down and to a side.

3.  Align the switch mounting plate holes with welded 

bosses and install the 3/8" x .75" (10M x 19 mm) 

long bolts with lock washers. Tighten bolts to the 

recommended torque, (refer to Table 4).

4.  Install Plastic Mounting Nut over the externally protrud-

ing threaded sealing gland and tighten plastic mounting 

nut (refer to Table 5). (Sealing is accomplished with 

O-rings on the operating shaft and gasketed sealing 

gland secured on the outside of the tank with locking 

nut).

5.  (Optional) install spring (small end toward end of shaft) 

and limit plate over the shaft.

6.  Install handle onto the switch shaft with the stainless 

steel hex socket cap screw and lock washer supplied 

and tighten to recommended torque in Table 4.

Table 4.  Recommended Torque (BOLT-IN)

Part

Torque Level

Mounting Bolts 
  [3/8" Dia.(10 mm)]

60-100 in-lbs (7-11 Nm)

Plastic Mounting Nut

60-120 in-lbs (7-14 Nm)

Switch Handle Bolt

40-60 in-lbs (5-7 Nm)

Figure 4.  Four-Position Bolt-Mount loadbreak switch 

(top/side view).

SWITCH BODY

(4 SPRING SHOWN)

CAP SCREW

(FURNISHED)

LOCKWASHER

(FURNISHED)

HANDLE

(FURNISHED)

SPRING

(FURNISHED)

LIMIT PLATE

(FURNISHED)

MOUNTING NUT

(FURNISHED)

4 WELD PINS

SEE FIGURE 10

(NOT FURNISHED)

4 WELD COUPLINGS

SEE FIGURE 10

(NOT FURNISHED)

TANK WALL

TANK SEALING GLAND

AND GASKET

(FURNISHED)

PLASTIC

HEX SOCKET

CAUTION 

The areas around the mechanisms and contacts do not 

contain user adjustable parts and should not be altered 

during installation.

CAUTION 

Bolt-In Assembly switches are dependent on proper 

location and use of couplings welded to the inside 

of tank. A reliable system of fixturing and gauging is 

essential to successful mounting of switch.

4

SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS

  MN800002EN   March 2016

Содержание COOPER POWER LS4R Series

Страница 1: ...Sectionalizing switch installation instructions COOPER POWER SERIES OEM Equipment MN800002EN Effective March 2016 Supersedes June 2015...

Страница 2: ...IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES...

Страница 3: ...Std C37 71 2001 standard 2 Ratings and characteristics table per IEC 60265 1 2 Dimensional information 2 INSTALLATION PROCEDURE Bolt In assembly 4 Ring Mount assembly 5 Connect internal leads 6 RECOM...

Страница 4: ...n Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low v...

Страница 5: ...aded activating mechanism ensures quick loadbreak action and positive contact engagement through all positions The Make Before Break MBB switches provide uninterrupted power during switching Read this...

Страница 6: ...n phases kV 95 125 150 Across open contacts kV 95 125 150 Power Frequency 1 minute To ground and between phases kV 35 60 70 Across open contacts kV 35 60 70 DC Withstand 15 minutes To ground and betwe...

Страница 7: ...n be used on 14 gauge 075 inch 1 9 mm to 25 inch 6 4 mm thick frontplate 14 gauge shown 3 Optional padlock handle is available See catalog section CA800005EN Table 6 and Figure 6 4 See catalog section...

Страница 8: ...ng is accomplished with O rings on the operating shaft and gasketed sealing gland secured on the outside of the tank with locking nut 5 Optional install spring small end toward end of shaft and limit...

Страница 9: ...ance zone and have an insulated barrier between them and the switch This barrier will deflect any gas bubbles generated by the switch operation The outline drawing shown in Figure 6 describes the swit...

Страница 10: ...B A A A A COIL B C COIL C COIL V BLADE MAKE BEFORE BREAK A C B A C B A C B A C B AB C B C OPEN A C LINES A B TO C LINE A ONLY LINE B ONLY TO C TO C OPEN ALL B A C COIL T BLADE BREAK BEFORE MAKE A C B...

Страница 11: ...d training may cause excess cantilever force and difficulty in switch operation Figure 6 Arc clearance zone Figure 7 View of tank front with optional limit plate positioned over pin Note With limit pl...

Страница 12: ...next position could jam the mechanism making the switch inoperable If the handle stops jams in a position between the designated marked positions stop switching operation and consult the factory prio...

Страница 13: ...adbreak devices Failure to follow this warning could result in equipment damage severe injury or death WARNING Hazardous voltage Do not operate loadbreak equipment if a fault condition is suspected Do...

Страница 14: ...This page is intentionally left blank 10 SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS MN800002EN March 2016...

Страница 15: ...This page is intentionally left blank 11 SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS MN800002EN March 2016...

Страница 16: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN800002EN Rev 01 Supersedes MN800002EN Rev 00 SAFETY FOR LIFE Eaton is a registered trademark All trademark...

Отзывы: