Figure 9. Hole and weld pin placement detail (Ring-
Mount design only).
Notes:
Pre-fabricated conversion plates available. Order P/N 2037424C04M.
Weld pins should not be used with optional pad-lockable handle.
* Exterior mounting surface must be flat within .010" (0.25 mm) over entire
area.
** Interior mounting surface must be clear of obstructions.
X = 36
Y = 0
ON EXTERIOR WALL:
.312" DIAMETER X 625" LONG
(8 mm) (16 mm)
(4) WELD PINS
RADIUS.140"
(4 mm)
3.00"
(76 mm)
TYPICAL
1.50"
(38 mm)
TYPICAL
3.00"
(76 mm)
TYPICAL
1.50"
(38 mm)
TYPICAL
.662"
(17 mm)
DIAMETER 2.00"
(51 mm)*
DIAMETER
6.25"
(159 mm)**
1.320"
+0.030
- 0.000
(33.5 mm
+0.8
)
- 0.0
DIA. HOLE
WARNING
Transformers use conventional transformer oil or
Envirotemp™ FR3™ fluid for an insulating liquid.
When the insulating liquid temperature is less than
-20 °C (-4 °F) for conventional transformer oil or less
than -10 °C (14 °F) for Envirotemp™ FR3™ fluid, the
increase in fluid viscosity may reduce make and
break capabilities of loadbreak devices. Below these
temperatures, under-oil loadbreak accessories should
not be used to
make
or
break
a
load
. Instead,
de-energize transformer from a remote upstream
source before operating under-oil loadbreak devices.
Failure to follow this warning could result in equipment
damage, severe injury, or death.
WARNING
Hazardous voltage.
•
Do not operate loadbreak equipment if a fault
condition is suspected. Doing so can cause an
explosion or fire.
•
Use a hotstick to operate transformer loadbreak
equipment.
•
After operating transformer loadbreak equipment,
check that voltages at transformer terminals are
the expected values. Checking voltages verifies that
loadbreak equipment operated properly and the
electrical circuit conditions are as expected.
•
Before servicing transformer secondary connected
equipment, verify that all transformer secondary
terminals have zero voltage and ground the
transformer secondary terminals following industry
accepted safe grounding practices. Grounding
secondary terminals protects against situations such
as a standby generator energizing transformer from
the secondary circuit.
•
Follow industry accepted safety practices. Utilize
protective clothing and equipment when working
with loadbreak equipment.
•
These recommendations are in addition to any
utility, end user, federal, state, local, or municipal
regulations which may apply.
•
Failure to follow this warning could result in
component failure, property damage, severe injury,
or death.
9
SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS
MN800002EN March 2016