1 CMD contactor monitoring device
1.3 Improper use
CMD(220-240VAC), CMDB
12/17 MN121002ZU-DEEN
www.eaton.com
25
The CMD relay can be combined with the following Eaton contactors, motor-
protective circuit-breakers and circuit-breakers:
•
Contactors/contact modules, fitted with an auxiliary NC contact as mirror
contact and an additional auxiliary NO contact.
•
DILM(C)7, DILM(C)9, DILM(C)12, DILM(C)15, DILM(C)17,
DILM(C)25, DILM(C)32, DILM(C)40, DILM(C)50, DILM(C)65,
DILM(C)72, DILM(C)80, DILM(C)95, DILM(C)115, DILM(C)150,
DILM(C)170.
•
DILEEM and DILEM.
•
DILM185A(-S), DILM225A(-S), DILM250(-S), DILM300A(-S),
DILM400(-S), DILM500(-S).
•
DILM580, DILM650, DILM750, DILM820, DILM1000.
•
DILH1400, DILH2000.
•
Motor-protective circuit-breaker, circuit-breaker and switch-disconnector,
fitted with an undervoltage release
•
NZM1, N1 + NZM1-XU(HIV20)(L)18DC
•
NZM2, N2 + NZM2/3-XU(HIV20)18DC
•
NZM3, N3 + NZM2/3-XU(HIV20)18DC
•
NZM4, N4 + NZM4-XU(HIV20)18DC
1.3 Improper use
The CMD contactor monitoring device has only been tested and approved in
combination with the Eaton contactors and circuit-breakers that are listed in
section 1.2, “System overview”, page 24.
→
The contactor must be provided with an auxiliary NC contact
that is designed as a mirror contact in accordance with IEC/EN
60947-4-1 Annex F.
The auxiliary NO contact and auxiliary NC contact must be
interlocked opposing in accordance with IEC/EN 60947-5-1
Annex L.
The contactor and the CMD are fed with the same control
voltage.
→
The CMD must therefore only be combined with these devices.