Device window – Web-Controller
10
Manual Touchscreen Controller
ZNO2038000 A www.eaton.com
GB
Status display of the device
Selected strand: All status messages in this window apply to strand 1.
Function test
Yellow = when at least one luminaire in the strand is currently undergoing a function test
Operating time test
Yellow = when at least one luminaire is currently undergoing an operating time test
Delayed emergency
lighting
Yellow = when at least one luminaire is still in delayed emergency lighting following a power
cut
Battery fault
Red = when at least one luminaire has a battery fault
Luminaire malfunction
Red = when at least one luminaire has an LED fault
Deferred operating time test
Red = when at least one luminaire has a deferred operating time test, because less than 24
hours earlier there was a partial discharge
Battery operation
Red = when at least one luminaire is battery operated
Communication
Red = when at least one luminaire has a communication disruption with the Controller
Blocked
Red = when at least one luminaire in the strand is blocked
Error in operating time test
Red = when at least one luminaire has not passed the operating time test (battery test)
Function test error
Red = when at least one luminaire has not passed the function test (luminaire test)
Deferred function test
Red = when at least one luminaire has deferred the function test, because a partial discharge
took place earlier
Total zone status
The configured zones and their total status are shown in the lower part of the window. In the
case of 4-strand operations this can be 2, 4, 5 or 8 zones and in the case of 2-strand opera-
tions 4, 8, 10 or 16 zones.
In CGLine compatibility mode only 1 zone is possible for each! By clicking on the correspond-
ing zone you access the zone image with the luminaires installed.
Status displays for the strand selected (red). Strand selection is made by clicking on
the strand number in the right strand status (blue).