17
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Compatible Equipment
Interfaces
The panel has been designed to be suitable for a wide range of applications, various
interfaces have been developed to enable the simple integration of other fire
systems or building control and safety systems . The following devices are available:
3 Channel I/O device
This interface has 3 input channels and 3 output channels . It is used to monitor up
to three separate inputs from equipment such as sprinkler flow switches and also
to provide 3 separately controlled volt free output contacts which are intended to be
used to control external equipment such as air
handling plant or access control systems .
All inputs and outputs operate completely
independently of each other and can be
programmed using the sophisticated cause and
effect capabilities to operate either globally or
in response to activation of specific devices or
specific inputs .
Inputs are monitored for open and short circuits .
A specific resistance is required to activate
an alarm condition, fully open or short circuit
conditions are monitored and generate a system
fault signal .
Inputs are suitable for use as fire signal inputs such as from a sprinkler flow
switch, however they can also be used to monitor non fire inputs such as external
keyswitches .
Outputs are rated to switch a maximum of 1A resistive at 30V DC .
It is supplied in a surface mounting IP65 box .
Single Channel I/O device with mains rated switching capability
This interface is a single channel input / output unit . The output is capable of
switching up to 8A at 230V AC . It is commonly
used for applications such as door release
controls and plant shut down signalling .
The input is monitored for open and short
circuits . A specific resistance is required to
activate an alarm condition, fully open or short
circuit conditions are monitored and generate a
system fault signal .
The input is suitable for use as a fire signal input
such as from a sprinkler flow switch . However it
can also be used to monitor non fire inputs such
as an external keyswitch .
It is supplied in a surface mounting IP65 box .