DeviceNet Configuration
26
C440/XTOE Electronic Overload Relay, DeviceNet
MN04210002E—March 2011 www.eaton.com
Control Supervisor Instance Attributes (C440), continued
Faulted/Tripped
A condition exists that is out of the normal operating range of the device. This condition has been configured to cause the
device to enter the faulted or tripped state.
Fault Reset
Commands the device out of the faulted state. A transition from 0 to 1 will cause the fault reset.
Faulted State
Attr ID
NV
Access Rule
Name
Data Type
Attribute Description
106
NV
Set
Comm fault
trip value
BOOL
User-defined value for use with comm fault
trip action attribute
0 = No affect
1 = Trip
107
NV
Set
Idle trip action
BOOL
Action taken on trip state in communication
idle state
0 = Use Idle trip value attribute
1 = No change
108
NV
Set
Idle trip value
BOOL
User-defined value for use with idle trip
action attribute
0 = No affect
1 = Trip
130
—
Get
Device feature status
WORD
The feature status bits are defined as follows:
Bit Feature
0,1:
Class index (00 = Class 10a; 01 = Class 10; 10 = Class 20; 11 = Class 30)
2:
Phase loss/imbalance enabled
3:
Ground fault enabled
4:
Auto reset enabled
5:
Remote reset active
8:
DIP switch position 0
9:
DIP switch position 1
10:
DIP switch position 2
11:
DIP switch position 3
12-15: Reserved
131
—
Get
Device temperature in
degrees
INT
Temperature as seen by the base device microcontroller, 10% accuracy
132
—
Get
Frequency
UINT
Line frequency measured by the device in deci Hz
Initial Value
Commanded Value
Result
0
0
No action
0
1
Reset fault
1
0
No action
1
1
No action