manualshive.com logo in svg
background image

6

3A1341RevB

Cooper Bussmann Power Module™ Switch

Transformer Fuse Table

* Specifications only apply to mechanical (screw) lugs. Attaching lugs and accessories to these devices

may require other torque specifications.

Power Module Voltage/

Primary

Secondary

Transformer Voltage

Fuse (amps)

Fuse (amps)

208/120

FNQ-R-2

FNM-1 1/4

240/120

FNQ-R-2

FNM-1 1/4

480/120

FNQ-R-1

FNM-1 1/4

600/120

FNQ-R-1

FNM-1 1/4

Lug Torque Specifications (Lb-In)

30A

60A

100A

200A

400A

Lugs*

PS

PS

PS

PS

PS

MCCB Lug Torque

50

50

50

200

275

Fuse Lug Torque

25

45

120

275

275

Neutral Lug Torque

35

45-120

120

275

500

Ground Lug Torque

35

45

50

375

375

Connection Table

Single Output - Fuse Installed

Primary

Secondary

Volt

Term.

Volt

Term.

Volt

Term

200 H4-H3

23

XF-X2

110

XF-X1

208 H4-H3

24

XF-X2

115

XF-X1

220 H4-H2

23

XF-X2

110

XF-X1

230 H4-H2

24

XF-X2

115

XF-X1

240 H4-H2

25

XF-X2

120

XF-X1

440 H4-H1

23

XF-X2

110

XF-X1

460 H4-H1

24

XF-X2

115

XF-X1

480 H4-H1

25

XF-X2

120

XF-X1

Note: If both outputs are used simultaneously,
fusing should be done off of the transformer,
with X3 replacing XF.

Move Lead H to Select Input Voltage

H1

H2

H3

H4

B100-2207-8

C0100E5EFB

X3

X2

XF

X1

Содержание Bussmann Quik-Spec

Страница 1: ...Power Module Switch Elevator Disconnect Instruction Leaflet Read and retain for future reference 3A1341RevB...

Страница 2: ...nance of the equipment 3 4 Catalog Number System 5 Transformer Fuse Specifications 6 Lug Torque Specifications 6 Wiring Options R1 F1 7 Options R1 F3 8 Options R2 F1 9 Maintenance 10 Notes 11 Customer...

Страница 3: ...ersion of this Instruction Leaflet download Instruction Leaflet from the Cooper Bussmann website at www cooperbussmann com PowerMod The contents of this Instruction Leaflet are not part of nor do they...

Страница 4: ...azardous situation which if not avoided could result in property damage Safety Concerns The following are important safety precautions that Power Modules Switch elevator disconnect users should observ...

Страница 5: ...3A1341RevB 5 Cooper Bussmann Power Module Switch Catalog Number System The following catalog numbering system defines a Power Module Switch construction B...

Страница 6: ...PS MCCB Lug Torque 50 50 50 200 275 Fuse Lug Torque 25 45 120 275 275 Neutral Lug Torque 35 45 120 120 275 500 Ground Lug Torque 35 45 50 375 375 Connection Table Single Output Fuse Installed Primary...

Страница 7: ...3A1341RevB 7 Cooper Bussmann Power Module Switch R1 F1 Options...

Страница 8: ...8 3A1341RevB Cooper Bussmann Power Module Switch R1 F3 Options...

Страница 9: ...3A1341RevB 9 Cooper Bussmann Power Module Switch R2 F1 Options...

Страница 10: ...F position to the ON position Verify that power is restored Inspection Keep switch exterior and interior clean Always follow prevailing safety rules when servicing this product throughout the year Per...

Страница 11: ...3A1341RevB 11 Cooper Bussmann Power Module Switch NOTES...

Страница 12: ...lication Engineering assistance is available to all customers The Application Engineering team is staffed by degreed engineers and available by phone with technical and application support Monday Frid...

Отзывы: