3A1341RevB

Cooper Bussmann Power Module™ Switch

Maintenance

To help assure proper operation of the Cooper Bussmann Power Module Switch, all
components should be tested and inspected on an annual basis by a qualified 
person. Cooper Bussmann suggests the following*:

Testing

• Performing these steps helps verify the Power Module Switch is properly operating. If

you are unable to successfully completed these steps, contact Cooper Bussmann.

• Make sure the system is energized and turned ON.

• Activate the fire alarm system contacts for shunt trip. (A fire alarm technician may be

required for this step.)  If the Power Module Switch has a key test switch, use it to shunt
trip the unit without activating the fire alarm system.

• Shunt trip will energize the fire alarm isolation relay and close contact points 4 and 7.

• Closuring relay points 4 and 7 will energize the shunt trip coil, opening the switch 

contacts, and actuating the switch and handle into the TRIP position.

• Verify that power is disconnected and the handle is in the TRIP position.

• Move the handle position to RESET, then allow handle to assume the OFF position.

• Move the handle from the OFF position to the ON position.

• Verify that power is restored.

Inspection

• Keep switch exterior and interior clean. Always follow prevailing safety rules when 

servicing this product throughout the year.

• Periodically check lug torque values and keep them in specification. The chart on page 6 

contains the torque values for the various switch amp ratings.

• Preventative maintenance should include a thermal-scan to uncover any portion 

generating excessive heat that indicates an underlying problem.

• Any unexpected temperature increase, not related to load variations or ambient 

temperature could signal a lug torque issue.

• Maximum temperature at any lug should never exceed 75°C under any operating 

condition or load.

*  Before performing any inspection or testing, notify affected building occupants that the elevator is

being taken out of service.

Electrical equipment may contain hazardous voltages. These
can cause electrical shock, burn or death.

Only qualified personnel should perform procedures involving 
electrical equipment. Always properly ground equipment and
lockout electric power (de-energize) before accessing electrical
equipment and enclosures. All deadfronts and other shielding
must be in place before energizing this disconnect switch.
Take note of and follow all safety instructions in this Instruction
Leaflet.

Electrical Shock
Hazard

Содержание Bussmann Quik-Spec

Страница 1: ...Power Module Switch Elevator Disconnect Instruction Leaflet Read and retain for future reference 3A1341RevB...

Страница 2: ...nance of the equipment 3 4 Catalog Number System 5 Transformer Fuse Specifications 6 Lug Torque Specifications 6 Wiring Options R1 F1 7 Options R1 F3 8 Options R2 F1 9 Maintenance 10 Notes 11 Customer...

Страница 3: ...ersion of this Instruction Leaflet download Instruction Leaflet from the Cooper Bussmann website at www cooperbussmann com PowerMod The contents of this Instruction Leaflet are not part of nor do they...

Страница 4: ...azardous situation which if not avoided could result in property damage Safety Concerns The following are important safety precautions that Power Modules Switch elevator disconnect users should observ...

Страница 5: ...3A1341RevB 5 Cooper Bussmann Power Module Switch Catalog Number System The following catalog numbering system defines a Power Module Switch construction B...

Страница 6: ...PS MCCB Lug Torque 50 50 50 200 275 Fuse Lug Torque 25 45 120 275 275 Neutral Lug Torque 35 45 120 120 275 500 Ground Lug Torque 35 45 50 375 375 Connection Table Single Output Fuse Installed Primary...

Страница 7: ...3A1341RevB 7 Cooper Bussmann Power Module Switch R1 F1 Options...

Страница 8: ...8 3A1341RevB Cooper Bussmann Power Module Switch R1 F3 Options...

Страница 9: ...3A1341RevB 9 Cooper Bussmann Power Module Switch R2 F1 Options...

Страница 10: ...F position to the ON position Verify that power is restored Inspection Keep switch exterior and interior clean Always follow prevailing safety rules when servicing this product throughout the year Per...

Страница 11: ...3A1341RevB 11 Cooper Bussmann Power Module Switch NOTES...

Страница 12: ...lication Engineering assistance is available to all customers The Application Engineering team is staffed by degreed engineers and available by phone with technical and application support Monday Frid...

Отзывы: