ote:
N
source drawing reference wiring diagram 286979 .
ote:
N
For kits with a green OFF light, an additional top added
NC auxiliary is needed to be supplied by the customer .
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
3
2
2
1
1
T1
62
61
F
T2
62
61
R
X2
X1
OFF
G
1 2
1 2 RED
RED
RED
BLK/WHT
BLK/WHT
R1
_/21/61
6/22/62
R
A2
A1
F
96
95
OL
98
97
OL
5/14/54
4/13/53
R1
R
L1
_/21/61
7/22/62
F
A2
A1
R
CUSTOMER
CONTROL
CIRCUIT
3/14/54
2/13/53
L1
F
RED
RED
RED
A2
A1
FWD/UP
R
A2
A1
REV/DWN
R
BLK/RED
BLK/RED
BLK/RED
BLK/RED
RED
RED
RED
RED
1 2
1 2
1 2
1 2
RED
(BLU/WHT
IF DC)
RED
(BLU IF DC)
RED (BLU IF DC)
RED
(BLU IF DC)
REV/FWD OR DWN/UP CUSTOMER CONTROL
OPTIONS SHOWN: REV/DWN LIGHT AND FWD/UP LIGHT, OFF LIGHT
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
TWO 2NO TOP ADDER AUX INCLUDED FOR ALL COIL VOLTAGES EXCEPT
WHEN OPTION FOR OFF LIGHT IS USED AND ONE 2NO TOP ADDER AUX
IS SWAPPED OUT FOR ONE 1NO-1NC.
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX IN PLACE OF 2NO AUX IN POSITION T1)
BLU
BLU
BLU
BLU
BLU/WHT
BLK/RED
BLK/RED
BLK/RED
A2
R PICKUP
A2
F PICKUP
X2
X1
REV/DWN
R
X2
X1
FWD/UP
R
A1
R HOLD
98
97
OL
96
95
OL
A1
F HOLD
WIRING FOR DC STARTERS ONLY
L1
F LATE OPENING
BLK/RED
R1
R LATE OPENING
T2
64
63
R
64
63
T1
F
T2
54
53
R
54
53
T1
F
4
CONTROL POWER WIRING NOTES
CAUTION
SEPARATE CONTROL POWER
COMMON CONTROL POWER
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 63 OR NO. 61 TERMINAL PER DIAGRAM ON THE TOP ADDER AUX. AND TO THE NO.
96 TERMINAL ON THE OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 OR NO. 63 TERMINAL PER
DIAGRAM ON THE TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER
DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
NOT INCLUDED FOR SEPARATE CONTROL COIL VOLTAGES 120V AND LESS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
NC1
NC2
OFF
NO4
NO3
ON
2/13
3/14
R1
M1
A2
A1
M1
X2
X1
RUN
R
1 2
X2
X1
OFF
G
1 2
R1
62
61
M1
1 2
1 2
BLK/RED
BLK/RED
RED
RED
RED
RED
BLK/WHT
BLK/WHT
RED
RED
YEL
BLK
RED
(BLU IF
DC)
RED
(BLU/WHT IF DC)
A2
A1
M2
LIGHTING 2 CONTACTOR/COIL REF.: OFF/ON OVAL PUSHBUTTON
RUN LIGHT AND OFF LIGHT
T1
54
53
M
1
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
1
7
Instructions and Operation
P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON
www.eaton.com