Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
107
3.
Press the
button to save the setting.
4.
Press the
ESC
button until the Start screen appears.
Table 15. Suggested Battery Low Alarm Level Settings
Warning Time
(in Minutes)
Number of EBMs
Installed
Battery Low Alarm Level (User Setting)
20% Load
50% Load
100% Load
2
1
1.783
1.821
1.854
2
1.776
1.811
1.831
3
1.772
1.798
1.818
4
1.768
1.781
1.805
3
1
1.805
1.848
1.891
2
1.793
1.833
1.859
3
1.787
1.820
1.843
4
1.781
1.803
1.831
4
1
1.822
1.868
1.918
2
1.807
1.850
1.883
3
1.789
1.836
1.866
4
1.793
1.818
1.850
5
1
1.835
1.884
1.941
2
1.818
1.863
1.903
3
1.799
1.849
1.883
4
1.803
1.823
1.865
NOTE
Values are approximate.
55..2200
R
Ruunnnniinngg A
Auuttoom
maattiicc B
Baatttteerryy TTeessttss
Battery tests may rely on backfeeding the utility, using the utility as a load. If the connected load is above 65%
the UPS will only use the load to do the test. Some sites may choose to disable battery testing if their source is
not capable of being backfed. Examples of such sources include generators, other UPSs, and other stiff or soft
sources.
If a source is not capable of being backfed, the UPS will abort the test (due to utility failure) and will maintain
the load and log the event. Further consequences depend on the source (for example, another UPS feeding the
BladeUPS module may trip off).
NOTE
For automatic and manual battery tests, the UPS determines when it is appropriate to
run the test. Battery tests run only when the system is in High Efficiency mode.
To disable battery testing:
Содержание BladeUPS none
Страница 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Страница 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Страница 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Страница 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Страница 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Страница 160: ...16420164914 164201649 14 ...