background image

20

Instruction Book    

IB182023EN   March 2016   www.eaton.com

AMH-4.76-VR

Replacement Circuit Breaker

 WARNING

KEEP HANDS OFF THE TOP EDGE OF THE FRONT BARRIER WHEN PUSHING 

A BREAKER INTO A CELL. FAILURE TO DO SO COULD RESULT IN BODILY 

INJURY, IF FINGERS BECOME WEDGED BETWEEN THE BREAKER AND 

THE CELL. USE THE HANDLES PROVIDED ON THE FRONT OF THE BREAKER 

FACEPLATE, OR USE BOTH FULLY OPENED HANDS FLAT ON THE FRONT OF 

THE FACEPLATE.

These checks can be performed with the breaker in its withdrawn 

or disconnect position and connecting the breaker to a test cabinet 

or to the switchgear cell’s secondary receptacle using the special 

extension cable designed for this purpose and described in Section 

3.
Perform electrical operations checks. Close and trip the circuit 

breaker electrically several times to verify that the operation is 

reliable and consistent. Check that the operation of the spring 

charging motor is reasonably prompt and that the motor makes no 

unusual noise.

 WARNING

DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE BREAKER 

IN THE “CONNECT” POSITION BECAUSE OF THE POSSIBILITY OF 

CONNECTING DE-ENERGIZED LOAD CIRCUITS TO THE ELECTRICAL POWER 

SOURCE, RESULTING IN DEATH, PERSONNEL INJURY OR EQUIPMENT

Sttp 11e:

  After an adjustment is made, make sure that all nuts are 

secured in place, prior to returning to service.

5.3   MANUAL OPERATION CHECK

Manual operational checks must be performed before the breaker  

is connected to an energized circuit. Tests must be performed with 

the breaker withdrawn from the cell or in the disconnect position. 

While the breaker is withdrawn or in the disconnect position, place 

the maintenance tool into the manual charge socket opening and 

charge the closing springs with about 36 up and down strokes of 

the handle. When charging is complete, the closing crank goes over 

center with an audible “click” and the springs Charged / Discharged 

Indicator shows “Charged”. Remove the maintenance tool.

 NOTICE

IF THE SPRINGS ARE TO BE CHARGED ON A CLOSED BREAKER, NO 

CLICK IS HEARD AT THE END OF CHARGING OPERATION. DISCONTINUE 

CHARGING AND REMOVE THE MAINTENANCE TOOL AS SOON AS 

“CHARGED” FLAG IS FULLY VISIBLE. CONTINUE ATTEMPTS TO FURTHER 

CHARGE MAY RESULT IN DAMAGE TO THE MECHANISM.

 WARNING

ALWAYS REMOVE THE MAINTENANCE TOOL AFTER CHARGING THE 

SPRING. FAILURE TO REMOVE THE MAINTENANCE TOOL FROM THE 

BREAKER COULD CAUSE INJURY TO PERSONNEL AND/OR EQUIPMENT 

DAMAGE IF THE BREAKER WAS TO CLOSE.

Close and trip the breaker by pushing the close lever then the trip 

lever (Figure 3.3).

5.4   VACUUM INTERRUPTER INTEGRITY

Using a dry lint-free cloth or a paper towel, clean all the insulating 

surfaces of the pole units. Conduct a vacuum interrupter integrity 

check as described in Section 6.

5.5   LOW FREQUENCY WITHSTAND TEST (INSULATION 

CHECK)

Check breaker primary and secondary insulation per Section 6.

5.6   CONTACT EROSION AND WIPE

Manually charge the closing springs and close the breaker. Check 

contact erosion and wipe as described in Section 6.

5.7   PRIMARY CIRCUIT RESISTANCE

Check the primary circuit resistance as described in Section 6. The 

resistance should not exceed the values specified. Record the values 

obtained for future reference.

5.8   ELECTRICAL OPERATIONS CHECK

After going through the above steps, the breaker is now ready to be 

operated electrically. It is preferred that this check be made with the 

breaker in the Test position in the breaker compartment.
Since the Type AMH-4.76-VR Circuit Breaker is for use in existing 

AMH Metal-Clad Switchgear, installation procedures are similar. If it 

is necessary to reference anything in the breaker compartment, refer 

to the original instruction books supplied with the assembly.

 WARNING

EXAMINE THE INSIDE OF THE CELL BEFORE INSERTING THE BREAKER 

FOR EXCESSIVE DIRT OR ANYTHING THAT MIGHT INTERFERE WITH THE 

BREAKER TRAVEL.

Figurt 5.2. AMH-VR in tht Disconntct Position

Содержание AMH-4.76-VR

Страница 1: ...March 2016 Instruction Book IB182023EN AMH 4 76 VR Replacement Circuit Breaker Supercedes October 2013 Effective AMH 4 76 VR 4 76 1200A Shown...

Страница 2: ...office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Ea...

Страница 3: ...BLOCK 13 4 7 INTERLOCKS 13 4 7 1 ANTI CLOSE INTERLOCK 13 4 7 2 RACKING SYSTEM TRIP AND SPRING RELEASE INTERLOCKS 13 4 8 MISCELLANEOUS ITEMS 15 4 8 1 MOC OPERATOR 15 4 8 2 OPERATIONS COUNTER 15 SECTION...

Страница 4: ...K RESPONSE CODE VR Series circuit breakers have a quick response code QR Code on the escutcheon of the circuit breaker cover This QR Code is a matrix barcode that provides direct access to download VR...

Страница 5: ...VR Replacement Circuit Breaker E H I G F J H D B C C A Table 2 AMH 4 76 VR Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J AMH 4 76 VR 250 250U 120...

Страница 6: ...nd or property damage Do not work on a breaker with the secondary test coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death personnel injury and...

Страница 7: ...eaker Style 94C9506G01 Racking Handle The racking handle is used to drive the racking mechanism which moves the circuit breaker into and out of the cell The original OEM racking handle will interface...

Страница 8: ...nual trip button The breaker will trip as shown by the breaker contacts open green indicator After completing this initial check leave the closing springs discharged and breaker contacts open Outdoor...

Страница 9: ...ont External View of AMH 4 76 VR Front External View 1 Manual Charging Socket 5 Guide Bar 9 MOC Actuator 2 Push To Close Button 6 Breaker Contacts Indicator 10 Push To Open Button 3 Racking Access Doo...

Страница 10: ...Replacement Circuit Breaker Figure 3 4 Rear External View of AMH 4 76 VR Rear External View 1 Shutter Actuator 4 SURE CLOSE Spring 7 Secondary Disconnect 2 Primary Disconnect 5 Guide Rail 8 Ground Con...

Страница 11: ...he vacuum to be quickly restored and prevents the transient recovery voltage from causing a restrike across the gap of the open contacts 4 1 1 THE INTERRUPTER ASSEMBLY Each interrupter is assembled at...

Страница 12: ...r positions shown in Figure 4 6 as follows a Breaker open closing springs discharged b Breaker open closing springs charged c Breaker closed closing springs discharged d Breaker closed closing springs...

Страница 13: ...ely retrofitted breakers Consequently it prevents the breaker from closing automatically even though the control close contact may have been made while the breaker is racked to the CONNECTED position...

Страница 14: ...een Test and Connect positions OPERATION C and NO C and NC C and NO C and NO C and NC C and NO Brown Switch Black Switch Black Switch Brown Switch SWITCH TERMINAL LS1 bb LS2 aa LS2 bb LC PS1 PS2 Break...

Страница 15: ...e breaker s MOC operator interfaces with the cell MOC switch in the same manner as the original breaker being replaced All VR Series breakers which are supplied with MOC operators are engineered with...

Страница 16: ...t Front Faceplate Removed 18WR Vacuum Element 1 LH Closing Spring 5 Spring Release Assembly 9 Manual Charge Socket 2 Motor Cutoff Switch 6 Shunt Trip Assembly 10 Ratchet wheel 3 Latch Check Switch Rea...

Страница 17: ...Spring Release Close Latch 6 Ratchet Wheel 11 Anti Close Interlock 2 Pole Shaft 7 Spring Crank 12 Motor Ratchet Lever 3 Closing Spring Fixed End 8 Cam Shaft 13 Spring Release Close Clapper 4 Closing...

Страница 18: ...g Spring Discharged 4 9 c Breaker Closed and Closing Spring Discharged 4 9 b Breaker Open and Closing Spring Charged 4 9 d Breaker Closed and Closing Spring Charged Charging Schematic 1 Main Link Roll...

Страница 19: ...he cell Maintenance usually means cleaning and lubricating the MOC mechanism If the MOC has seen a large number of cycles however worn components may have to be replaced To insure the proper operation...

Страница 20: ...an audible click and the springs Charged Discharged Indicator shows Charged Remove the maintenance tool NOTICE IF THE SPRINGS ARE TO BE CHARGED ON A CLOSED BREAKER NO CLICK IS HEARD AT THE END OF CHAR...

Страница 21: ...ndicator reads OPEN d Push the circuit breaker into the cell until the mechanical stop is reached this will be indicated by an audible click At this point the side plunger has fallen into the front sl...

Страница 22: ...the breaker can be operated either electrically or mechanically Remove rotary racking handle before performing any testing b To further remove the breaker to the disconnect position continue turning...

Страница 23: ...ted Withstand 1125V 60Hz For 1 Minute Hipot Tester Clean And Retest Or Replace 2 Power Element Vacuum Interrupters Contact Erosion Visibility Of Mark Visual Close The Breaker And Look For Green Mark O...

Страница 24: ...ential test is recommended a DC test may be performed if only a DC test unit is available but is not recommended In this case the equipment must be capable of delivering 5 milliamperes for one minute...

Страница 25: ...the primary circuit Open the breaker Connect the high potential lead of the test machine to one of the poles of the breaker Connect the remaining poles and breaker frame to ground Start the machine w...

Страница 26: ...nergy available in terms of over travel in inches to close the breaker contacts to their full extent It may be used periodically to monitor the health of the mechanism General Information The CloSure...

Страница 27: ...uit breaker then close it then reopen it Verify that the mark made in Step 7 is aligned with the pen opening If it is not aligned this indicates a problem with the circuit breaker stop the test and co...

Страница 28: ...Sharpie 15o Left and Right Figure 6 13 Top view of Cam and Marker Interface Cam Marker CloSure Tool TM 15O 15O Figure 6 10 With Marker in Hole C While Closing Breaker Figure 6 8 Manually Charging Clo...

Страница 29: ...cam shaft the main link and the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be dis...

Страница 30: ...Cut Off Contacts Open Or Burned Trip Coil Assembly Clapper Fails To Reset Closing Sound But No Close Pole Shaft Not Open Fully Trip Latch Reset Spring Damaged Or Missing Trip Bar D Shaft Fail To Rema...

Страница 31: ...Breaker Auxiliary Switch 94C9525G13 5 BREAKER POSITION SWITCH Breaker Position Switch PS1 94C9525H06 6 BREAKER POSITION SWITCH Breaker Position Switch PS2 94C9525H07 7 LATCH CHECK SWITCH Latch Check...

Страница 32: ...levard Cleveland OH 44122 United States Eaton com 2013 Eaton All Rights Reserved Printed in USA Publication No IB182023EN March 2016 Eaton is a registered trademark All trademarks are property of thei...

Отзывы: