COIL CHANGING
1. Remove Overlaod Relay/Contactor assembly from enclosure, after loosening the two mounting plate screws.
2. Slacken off screws at L3 and 13 and withdraw wiring.
3. Slacken off screws at T1, T2 and T3.
4. Tilt overload away from contactor and unclip mouldings to release Overload Relay from Contactor.
5. Slacken off screws at 14, L1, A1 and A2 to remove wires.
6. Undo slotted screws located below terminals L3 and T2.
7. Seperate top and bottom halves of Contactor and withdraw coil assembly.
8. Fit new coil assembly noting that the printing on the moulding is positioned at the top of the Contactor.
9. Re assemble in the reverse order ensuring that all wires are re attached to their correct terminals. See table on
front page. For slotted contactor assembly screws (item 6) re tighten to 1.2 Nm.
NOTE: When attaching Overload to Contactor ensure that the hook on the Overload engages with the Contactor and
is tilted into position before tightening screws at T1, T2 and T3.
MOTOR
CONNECTIONS
MOUNTING PLATE
FIXING SCREW
SUPPLY
CONNECTIONS
OVERLOAD RELAY
EARTH TERMINAL
MOUNTING PLATE
FIXING SCREW
3
5
1
13
L1
L3
L2
T1
T2
T3
2
4
6
14
98
97 95
96
2
4
6
17
18
For connection see diagrams opposite.
The main incoming terminals
1, 3, 5 are at the top of the contactor.
The main outgoing (motor) terminals
2, 4, 6 are at the bottom of the
overload relay.
A1 COIL CONNECTION
BELOW TERMINAL 1
A2 COIL CONNECTION
BELOW TERMINAL 14
INSTALLATION
See Important Notes on page 1 and note that the control circuit voltage should not exceed the nominal voltage by
more than 10% and should not be more than 15% below the nominal voltage.
1. Remove starter cover and relay/contactor assembly by loosening mounting plate fixing screws.
2. Remove appropriate knockout for cable entry.
3. Fix starter to wall using appropriate fixings and install cable tails as appropriate.
4. Connect cable tails to relay and contactor.
5. Refit relay/contactor assembly to enclosure and tighten mounting plate fixing screws.
6. Ensure cables are neatly routed and refit starter cover.
NOTE: DRAWN AS TYPE 1828ADS