Instruction Leaflet 

IL15465

Effective May 2011

A200 Size 3 or 4, 3  Pole Motor Controller

EATON CORPORATION

 www.eaton.com

AUXILIARY CONTACTS - TYPE J (Cont.)

A maximum of four auxiliary units can be installed with ter-

minals either in line or in a right angle relationship to the power 

poles. Auxiliary contacts mount by means of a spring clip and 

retainer screw. To remove the unit rotate the retainer screw several 

times (counterclockwise) and then slide the auxiliary contact unit 

out of the recess.

TYPE A OVERLOAD RELAY (See Figure 3)

The A200 motor controller can be equipped with a Type A block 

type non-ambient compensated overload relay (unmarked and 

with red reset rod) or with a block type temperature compensated 

overload relay (marked “ambient compensated” and with gray 

reset rod). The relay is of the bimetal actuated type equipped with 

trip indicator, trip adjustment covering ± 15% of rating and a 

normally closed control contact. It may be operated with either 

hand or automatic reset.

Reset operation is determined by the position of the plate on 

the load side of the overload base. Position the reset plate away 

from the panel to set the “hand” position. Loosen the locking 

screw, move the reset plate toward the panel, and retighten the 

screw to set the “auto” position.

Automatic reset should not be used with 2-wire control circuits 

where automatic starting of the motor may be hazardous

AUXILIARY CONTACTS - TYPE J (Cont.)

This A200 motor controller is usually equipped with a Type B 

block type ambient compensated overload relay (with gray reset 

rod). The controller can also be supplied with a non-ambient 

compensated overload relay (with red reset rod). The relay is of 

the bimetal actuated type equipped with a normally closed 

control contact. An optional isolated normally open control circuit 

is available for field mounting. When the overload relay trips, a 

yellow dot will appear flush with the molded surface below the 

reset rod. Resetting the relay returns this indicator to its normal 

concealed position.

HEATERS

Heaters are not included with the motor controller and must 

be ordered separately per the heater selection table and the 

information listed below. When installing heaters be sure that 

connecting surfaces are clean and heaters are attached securely 

to the relay in the proper location with the screws provided. The 

trip rating of a heater in a 40°C ambient is 125% of the minimum 

full load current shown in Table 1. When tested at 600 percent of 

its trip rating, the relay will trip in 20 seconds or less.

WARNING: 

To provide continued protection against fire and 

shock hazard, the complete overload relay must be replaced if 

burnout of a current element occurs. See Table II.