Eaton 9PX Lithium-Ion
P-164001006—Rev 01
35
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm
personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
3.
Plug the EBM cable(s) into the battery connector(s). Up to four EBMs may be connected to the UPS.
4.
Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
5.
Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
66..33
R
Reeppllaacciinngg tthhee U
UP
PS
S EEqquuiippppeedd w
wiitthh aa H
HoottS
Sw
waapp M
MB
BP
P
The
HotSwap MBP
module makes it
possible to service or even replace
the UPS without affecting the connected
loads.
1. Set switch
33
to Bypass position.
The red LED on the
HotSwap MBP
module goes ON, indicating that the
load is supplied directly with AC input
source power.
2. Stop the UPS by pressing the
button on the UPS control panel.
LED
31
"UPS ON - OK to switch"
goes OFF, the UPS can now be
disconnected and replaced.
Return to normal operation
1. Check that the UPS is correctly
connected to the
HotSwap MBP
module.
2. Start the UPS by pressing the
button on the UPS control panel.
LED
31
"UPS ON - OK to switch" on
the
HotSwap MBP
module goes ON
(otherwise, there is a connection error
between the
HotSwap MBP
module
and the UPS).
3. Set switch
33
to Normal position.
The red LED on the
HotSwap MBP
module goes OFF.
MBP-120
LOAD
15
28
1
8
2
4
3
5
6
9
10
11
7
29
33
34
35 36
Maintenance
66..44
R
Reeccyycclliinngg TThhee U
Usseedd EEqquuiippm
meenntt
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.