7 1
mini-Slot Cards
The Eaton 9EHD UPS has two standard, factory-installed Mini-Slot communication bays. See Figure 4-9 for bay
locations. The UPS is compatible with the following Mini-Slot cards (see Figure 7-1):
•
Network Management Card and Modbus/Jbus – provides remote monitoring through a Web browser
interface, e-mail, and a network management system (NMS) using SNMP and connects to a twisted-pair
Ethernet (10/100BaseT) network. The card also provides direct integration of UPS information (meters and
status) to a Building Management System (BMS) using the Modbus RTU protocol.
•
Network Management Card – provides remote monitoring through a Web browser interface, e-mail, and a
network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT)
network.
•
Management Card Contact and RS232 / Serial – two types of interfaces via a DB9 connector are available
with this card. Dry contact mode provides a simple way to transmit UPS information to an alarm system,
PLC, or computer system via dry relay contacts. The transmitted information is load powered, load on bypass,
load on battery, load on utility, battery fault, and low battery. RS232 mode provides an RS232 interface for
connection to a PC or to a UPS Control display unit. Jumpers are used to select the interface (contacts or
RS232).
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.
The Industrial relay Card-MS (IRC-MS) provides a simple way to remotely input UPS information to an alarm
system, PLC or a computer system via dry contacts. It offers five isolated dry contact outputs and one isolated
dry contact input.
Relays K1 through K5 are identical in function. Each output contact function can be assigned by the customer.
The UPS information is also configurable.
For installation and setup of a Mini-Slot card, contact an Eaton service representative (see paragraph 1.8). Refer
to the manual supplied with the Mini-Slot card for user instructions.
figure 7-1 optional mini-Slot Cards
For
Management Card Contact and
RS232/Serial
Network Management Card and
Modbus/Jbus
Network Management Card
Chapter 7 Communication
This chapter describes the communication features of the Eaton 9EHD UPS. For terminal wiring information,
see paragraph 3.2.3 and paragraph 4.4. For location of the customer interface panel and terminals, see
Figure 4-9 and Figure 4-10.
Eaton 9EHD UPS (20-40 kVA, 380/400/415V) Installation and Operation Manual