background image

DPD-9E2305

9

1.

2.

1.

2.

4.4  UPS connection

Power supply connection

Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source 

and the true electrical consumption of the total load.

For 9E1000IR and 9E2000IR:

Connect the UPS input socket 

 to the AC-power 

source using the cable of the protected equipment.
Connect the loads to the UPS using the cables 

.

For 9E3000IR:

Connect the supplied cable 

 to the socket 

, then 

to the AC-power source.
Connect the loads to the UPS using the cables 

, for 

high-power devices choose the 16A outlet. 

4.5  Register warranty

Register warranty at 

https://www.pqproductregistration.eaton.com

 

5  Interfaces and communication

5.1  Control panel

The screen provides useful information about the UPS itself, load status, events, measurements and settings.

 Power ON indicator (green) 

 On battery indicator (orange)

 On bypass indicator (orange)

 Alarm indicator (red)

 Escape

 Up

 Down

 Enter

 On/Off button

Содержание 9E1000IR

Страница 1: ...Eaton 9E Rack Advanced User Guide Copyright 2023 EATON All rights reserved DPD 9E2305 English 9E1000IR 9E2000IR 9E3000IR 9EEBM72R...

Страница 2: ...4 UPS connection 9 4 5 Register warranty 9 5 Interfaces and communication 9 5 1 Control panel 9 5 2 LCD description 10 5 3 Display functions 11 5 4 User settings 12 5 5 Communication ports 15 5 6 UPS...

Страница 3: ...ies 19 7 4 Replacing batteries 20 7 5 Recycling the used equipment 21 8 Troubleshooting 22 8 1 Typical alarms and faults 22 8 2 Service and support 24 9 Specification and technical characteristics 24...

Страница 4: ...nt a risk of energy or electrical shock or burn from high short circuit current Observe proper precaution Batteries may contain HIGH VOLTAGE and CORROSIVE TOXIC and EXPLOSIVE substances Information ad...

Страница 5: ...you to visit our web site at eaton com or contact your Eaton local representative 2 1 Environmental protection Eaton has implemented an environmental protection policy Products are developed according...

Страница 6: ...e sags impulsive transients line noise and long term under and over voltage conditions frequency variations switching transients and harmonic distortion Power outages can occur when you least expect i...

Страница 7: ...ion Weights kg lbs Dimensions mm inch D x W x H 9E1000IR 17 6 38 8 438 x 438 x 86 5 17 2 x 17 2 x 3 4 9E2000IR 29 9 63 9 608 x 438 x 86 5 23 9 x 17 2 x 3 4 9E3000IR 31 3 68 3 608 x 438 x 86 5 23 9 x 1...

Страница 8: ...ended Battery Module for 9E2000IR and 9E3000IR Network M2 Network M3 Eaton Gigabit Network Card SNMP v1 v3 and IP v4 v6 Ethernet 10 100 1000BaseT INDGW M2 Eaton Industrial Gateway Card Modbus TCP RTU...

Страница 9: ...ays of receipt of the equipment Send a copy of the damage claim within 15 days to your service representative Check the battery recharge date on the shipping carton label If the date has passed and th...

Страница 10: ...ounting on the rails The rails and necessary hardware are supplied by Eaton Screw the rail on the back of the rack Screw the rail on the front of the rack using the two holes at the bottom Screw the e...

Страница 11: ...only with 9E2000IR and 9E3000IR UPS UPS must be switch off and disconnected from the power supply prior to battery installation Only qualified service personnel is allowed to install the EBM when UPS...

Страница 12: ...he UPS using the cables For 9E3000IR Connect the supplied cable to the socket then to the AC power source Connect the loads to the UPS using the cables for high power devices choose the 16A outlet 4 5...

Страница 13: ...y dims after 5 minutes of inactivity Press any button to restore the screen Note If other indicator appears see troubleshooting page for additional information The following table describes the Operat...

Страница 14: ...and alarms show string but other faults only show code 5 3 Display functions Press the Enter button to activate the menu options Use the two middle buttons and to scroll through the menu structure Pr...

Страница 15: ...ontinuous data on the KWh kilowatt hour that connected equipment has consumed in the last one hour period 5 4 User settings The following table displays the options that can be changed by the user Mai...

Страница 16: ...e buzzer if an alarm occurs Enabled In Out settings Output voltage 200V 208V 220V 230V 240V 230 V Output frequency Auto sensing Frequency Converter 50Hz Frequency Converter 60Hz Auto sensing HE Mode E...

Страница 17: ...matic restart when utility returns after a UPS shutdown due to an extended power outage 0 Battery low capacity Capacity 0 100 The alarm triggers when the set percentage of battery capacity or remainin...

Страница 18: ...mmunicate with Eaton power management software You can improve the remote monitoring and power managment of the UPS by adding a communication card compatible with the 9E product Please note that cable...

Страница 19: ...capability as the Gigabit Network card Relay MS card provides isolated dry contact Form C relay outputs for UPS status Utility failure Battery low UPS alarm OK or on Bypass INDRELAY MS The Industrial...

Страница 20: ...arge The UPS charges the battery as soon as it is connected to the AC outlet whether the ON OFF button is pressed or not It is recommended that the UPS be permanently connected to the AC power supply...

Страница 21: ...inutes The UPS transfers to Bypass mode when the user activates Bypass mode through the front panel the UPS detects an internal failure the UPS has an overtemperature condition the UPS has an overload...

Страница 22: ...service life varies depending on the frequency of usage and ambient temperature life divided by 2 each 10 C above 25 C If the UPS requires any type of transportation verify that the UPS is turned off...

Страница 23: ...s for disposal requirements Do not dispose of batteries in a fire When exposed to flame batteries may explode Do not open or mutilate the battery or batteries Released electrolyte is harmful to the sk...

Страница 24: ...ection Reassemble in the reverse order finally follow instructions Testing new batteries below Testing new batteries To test new batteries Charge the batteries for 48 hours Press any button to activat...

Страница 25: ...rms may be announced by a beep in a regular way Example Battery low Faults are announced by a continuous beep and red LED Use the following troubleshooting chart to determine the UPS alarm condition 8...

Страница 26: ...pacity greater than 100 of nominal see User Settings for specific output overload ranges Remove some of the equipment from the UPS The UPS continues to operate but may shut down if the load increases...

Страница 27: ...A number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged i...

Страница 28: ...c with line 5 of nominal line frequency outside this range 0 5 of auto selected nominal frequency 0 2Hz of auto selected nominal frequency Nominal output 200 208 220 230 240V Nominal Frequency 50Hz or...

Страница 29: ...0 4 4 EFT 4 kV IEC 61000 4 5 Surges 2 kV Differential Mode 4 kV Common Mode IEC 61000 4 6 Electromagnetic field 10 V IEC 61000 4 8 Conducted magnetic field 30 A m UPS enclosure IP rating IP20 Earthing...

Страница 30: ...conversion Normal AC source Normal source of power for the UPS OVL Overload When the load exceeds 100 of the maximum load of the UPS UPS Uninterruptible Power System Bypass AC source Source supplying...

Отзывы: