OPERATION
EATON
9130 (9910-E15/E16) UPS Installation Guide for IBM
®
Applications
S
164201783 Rev 2
24
Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
Press any button on the front panel display to activate the menu
options, then select SETTINGS, USER SETTINGS, and NUMBER OF
BATTERY STRINGS.
2.
Use the or buttons to select the number of battery strings
according to your UPS configuration:
All UPS and EBM Cabinets
Number of Battery Strings
UPS only (internal batteries)
1 (default)
UPS + 1 EBM
3
UPS + 2 EBMs
5
UPS + 3 EBMs
7
UPS + 4 EBMs
9
NOTE
If 0 is selected, no batteries are connected and all battery-related
alarms are disabled.
NOTE
The UPS contains one battery string; each EBM contains two battery
strings.
3.
Press the
button to save the setting.
4.
Press the
ESC
button until the start screen appears.
Содержание 9910-E16
Страница 2: ...This page intentionally left blank ...
Страница 3: ...Eaton 9130 9910 E15 E16 UPS Installation Guide for IBM Applications ...
Страница 31: ...Eaton 9130 9910 E15 E16 UPS Asennusopas IBM sovelluksille ...
Страница 60: ...Onduleur 9910 E15 E16 Eaton 9130 Guide d Installation pour Applications IBM ...
Страница 91: ...Eaton 9130 9910 E15 E16 USV Installationshandbuch für IBM Anwendungen ...
Страница 120: ...UPS Eaton 9130 9910 E15 E16 Guida all installazione per applicazioni IBM ...
Страница 149: ...Zasilacz UPS Eaton 9130 9910 E15 E16 Instrukcja instalowania dla zastosowań IBM ...
Страница 182: ...ИБП Eaton 9130 9910 E15 E16 Руководство по установке в системах IBM ...
Страница 215: ...SAI Eaton 9130 9910 E15 E16 Guía de instalación para aplicaciones IBM ...
Страница 244: ...Eaton 9130 9910 E15 E16 UPS Installationshandledning för IBM applikationer ...