![Eaton 93PM Series Скачать руководство пользователя страница 89](http://html.mh-extra.com/html/eaton/93pm-series/93pm-series_installation-and-operation-manual_527114089.webp)
Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
77
55..22..44
B
Byyppaassss M
Mooddee
CAUTION
The critical load is not protected from voltage or frequency fluctuations or power outages while the UPS is in
Bypass mode.
The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure (if
configured for capacity). If configured for redundancy (N+1) the UPS would remain on line in Normal mode if
one UPM failed. The UPS can also be transferred from Normal mode to Bypass mode manually. The bypass
source supplies the commercial AC power to the load directly.
shows the path of electrical power
through the UPS system when operating in Bypass mode.
In Bypass mode, the output of the system is provided with three-phase AC power directly from the system
input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or
power outages from the source. Some power line filtering and surge protection is provided to the load but no
active power conditioning or battery support is available to the output of the system in the Bypass mode of
operation.
The internal bypass is comprised of a solid-state, silicon-controlled rectifier (SCR) continuous duty static switch,
and bypass switchgear. The static switch is used instantaneously anytime the inverter is unable to support the
applied load. The continuous static switch is wired in series with the bypass switchgear, and together they are
wired in parallel with the rectifier and inverter.
The static switch, being an electronically-controlled device, can be turned on immediately to pick up the load
from the inverter while the inverter switchgear opens to isolate the inverter. The bypass switchgear is normally
closed, ready to support the static switch unless the bypass input source becomes unavailable.
If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention,
the UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute period).
The fourth transfer attempt locks the critical load to the bypass source and requires operator intervention to
transfer.
Figure 41. Path of Current Through the UPS in Bypass Mode
Bypass Input
Rectifier Input
Output
Bypass Switchgear
Rectifier
Switchgear
Inverter
Switchgear
Battery
Switchgear
Closed
Open
Main Power Flow
Trickle Current
Energized
De-Energized
Switchgear
Rectifier
Inverter
Static
Switch
Battery Converter
Battery
Содержание 93PM Series
Страница 4: ......
Страница 22: ...10 Eaton 93PM UPS 480V Three Wire 100 kW Frame Installation and Operation Manual 164000227 Rev 07 Introduction ...
Страница 134: ...122 Eaton 93PM UPS 480V Three Wire 100 kW Frame Installation and Operation Manual 164000227 Rev 07 Communication ...
Страница 138: ...16400022707 164000227 07 ...