UPS Installation Plan and Unpacking
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-19
Table 3-7. Recommended Input Circuit Breaker Ratings
93E-15
80% Derated
29A
100% Rating
23A
93E-20
80% Derated
38A
100% Rating
31A
93E-30
80% Derated
57A
100%Rating
46A
93E-40
80% Derated
77A
100% Rating
61A
93E-60
80% Derated
115A
100% Rating
92A
93E-80
80% Derated
153A
100% Rating
123A
Circuit Breaker Rating
UPS Model
Load Derating
400V
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table 3-7 in accordance with local regulations.
Table 3-8. Recommended Bypass and Output Circuit Breaker Ratings
Circuit Breaker Rating
UPS Model
Load Derating
400V
93E-15
80% Derated
27A
100% Rating
22A
93E-20
80% Derated
36A
100% Rating
29A
93E-30
80% Derated
54A
100% Rating
43A
93E-40
80% Derated
72A
100% Rating
58A
93E-60
80% Derated
108A
100% Rating
87A
93E-80
80% Derated
144A
100% Rating
115A
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in Table 3-5. The recommended line-to-line load unbalance is 50% or less.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the recommended rating for bypass
and output circuit breakers.
Содержание 93E UPS
Страница 1: ...15 80 kVA 380 400 415V Installation and Operation Manual Eaton 93E UPS...
Страница 2: ......
Страница 4: ......
Страница 21: ...Section 1 Installation...
Страница 22: ......
Страница 66: ...UPS System Installation 4 20 Eaton 93E UPS 15 80 kVA 380 400 415V Installation and Operation Manual Notes...
Страница 67: ...Section 2 Operation...
Страница 68: ......
Страница 109: ......
Страница 110: ...614 01802 00...