Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
79
3.
To locate the appropriate terminals and review the wiring and termination requirements, see:
UPS System Interface Wiring Preparation
,
Distributed Bypass Power Wiring Preparation
and
.
4.
Route and install CAN wiring between the UPS cabinets. See
and
for wiring
information.
Table 18. External Parallel CAN Connections
Terminal
Terminal #
Name
Description
Recommended Wire Size
Max/Min
[Recommended]
CN13
1
GND-E**
Input/Output: External Parallel CAN
connections.
Max Wire = 14AWG / Min Wire =
30AWG
[Twisted Wires (3) #18 AWG]
2
GND-ISO**
3
CANBL**
4
CANBH
CN15
1
CANBL
CAN Termination jumper*.
Max Wire = 14AWG / Min Wire =
30AWG
[#18AWG Jumper (if used)]
2
CANBL_1
*On first and last installed UPS.
** Shared terminal if the UPS is connected between the first and last UPS
Table 19. CAN Wire Terminations
From UPS 1
To UPS 2
To UPS 3 (If Installed)
To UPS 4 (If Installed)
CN13 (GND-ISO)
CN13 (GND-ISO)
(Shared)
CN13 (GND-ISO)
(Shared)
CN13 (GND-ISO)
CN13 (CANBL)
CN13 (CANBL)
(Shared)
CN13 (CANBL)
(Shared)
CN13 (CANBL)
CN13 (CANBH)
CN13 (CANBH)
(Shared)
CN13 (CANBH)
(Shared)
CN13 (CANBH)
(Shared)
Содержание 9395XC
Страница 8: ......
Страница 16: ...xvi Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Figures ...
Страница 18: ...xviii Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Tables ...
Страница 26: ...8 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Introduction ...
Страница 118: ...100 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Understanding UPS Operation ...
Страница 160: ...16400107901 164001079 01 ...