Prreeppaarraattiioonn
NOTE
For full-rated operation of a Distributed Bypass System when in Bypass or ESS mode,
the line frequency impedance of all conduction paths must be equal when assessed
from the point where the grounded wire source connects to the System Switchgear to
the point where the Common Load connects to the System Switchgear.
Read and understand the following notes while planning and performing the installation:
•
All distributed bypass UPS rectifier inputs must come from one source and all bypass input feeds must
come from one source.
•
The 9395XC unit is designed for operation on a ground wire source of supply. There is no additional
connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral
loads.
•
The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary contacts for control of
the system.
•
Use the applicable wiring for the designated interface terminals:
33..33
IInnssppeeccttiinngg aanndd U
Unnppaacckkiinngg tthhee U
UP
PS
S C
Caabbiinneettss
The UPS cabinet is divided into two sections palleted separately for shipping. The sections are shipped bolted
to wooden pallets (see
and
) and protected with outer protective packaging material.
The UPS sections are heavy (see
). If unpacking and unloading instructions are not closely followed, the
cabinets may tip and cause serious injury.
AVERTISSEMENT!
Les sections de l’onduleur sont lourdes (voir le
). Suivre attentivement les instructions de déchargement
et de déballage pour eviter de renverser les armoires, ce qui pourrait causer de graves blessures.
To prevent damage to the wiring in the I/O section base when lifting or moving the cabinet:
•
Lift and move the I/O section using only the front or rear forklift slots.
•
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots. DO NOT
angle fork tips upward.
•
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
•
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are kept
in a horizontal position with no upward angling.
•
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
•
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring will occur.
Содержание 9395XC
Страница 8: ......
Страница 16: ...xvi Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Figures ...
Страница 18: ...xviii Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Tables ...
Страница 26: ...8 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Introduction ...
Страница 118: ...100 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Understanding UPS Operation ...
Страница 160: ...16400107901 164001079 01 ...