UPS MAINTENANCE
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
90
11.
Disconnect the batteries from the wiring, and loosen the 3 nylon
straps. Retain the wiring, straps, spaces and vinyl caps. See
Figure 46 and Figure 47.
12.
Remove the batteries from the tray. See “Recycling the Used
Battery or UPS” on page 94 for proper disposal of the batteries.
13.
Verify that the batteries to be installed are the type listed in
“Battery Type” on page 84. Use batteries of the same age, type,
and manufacturer so that UPS performance is not affected.
14.
Verify that 12 vinyl caps are installed on the battery tray dividers as
shown in Figure 46.
15.
Insert eight batteries into the battery tray (see Figure 47).
16.
Connect the batteries in the tray as shown in Figure 46 and
Figure 47.
17.
Secure the batteries to the tray, using 5 spacers and 3 nylon straps.
See Figure 46 and Figure 47 for spacer and strap placement.
Nylon Straps
(3)
Vinyl Caps (12)
Spacers (5)
Figure 46. Battery Tray without Batteries
Содержание 9355-F47 Unirom
Страница 1: ...Eaton 9355 F47 Unirom UPS 10 15 kVA User s Guide ...
Страница 4: ......
Страница 28: ...UPS SETUP Eaton 9355 F47 Unirom UPS 10 15 kVA User s Guide S 164201642 Rev C www eaton com powerquality 22 ...
Страница 78: ...COMMUNICATION Eaton 9355 F47 Unirom UPS 10 15 kVA User s Guide S 164201642 Rev C www eaton com powerquality 72 ...
Страница 88: ...OPERATION Eaton 9355 F47 Unirom UPS 10 15 kVA User s Guide S 164201642 Rev C www eaton com powerquality 82 ...
Страница 106: ...SPECIFICATIONS Eaton 9355 F47 Unirom UPS 10 15 kVA User s Guide S 164201642 Rev C www eaton com powerquality 100 ...
Страница 110: ...TROUBLESHOOTING Eaton 9355 F47 Unirom UPS 10 15 kVA User s Guide S 164201642 Rev C www eaton com powerquality 104 ...